Parameter

{Factory setting}

Setting value / Description / Note

Device

Supervisor

Parameter
set

P106

Ramp smoothing

(Ramp smoothing)

S

P

0 ... 100 %

{ 0 }

This parameter enables a smoothing of the acceleration and deceleration ramps. This is
necessary for applications where gentle, but dynamic speed change is important.

Ramp smoothing is carried out for every setpoint change. The value to be set is based on the set
acceleration and deceleration time, however values <10% have no effect.

The following then applies for the entire acceleration or deceleration time, including rounding:

 

100%

%

P106

P102

P102

TIME

ATION

ACCELER

tot

t

t

t

 

100%

%

P106

P103

P103

TIME

ON

DECELERATI

tot

t

t

t

P102

P103

Output

frequency

Desired

frequency

Time

each
10

– 100% of P102

each
10

– 100% of P103