5 Commissioning

BU 0180 GB-0914

Pre-series version

67

5.2.2.2

DIP switch configuration of the inverter

The analog inputs in the frequency inverter are suitable for current and voltage setpoints. For correct
processing of current setpoints (0-20mA / 4-20mA) the relevant DIP switch (S1) must be set for current
signals ("ON").

Adjustment to fail-safe signals in case of cable breaks (2-10V/4-20mA) is made via parameters 402 and 403.

A second DIP switch (S2) is also available, via which the system bus address can be specified or the
system bus can be activated. This has priority over the parameters P509, P514 and P515.

No.

Bit

DIP switch (S2)

2/1

2

1/0

ADR

System bus
address/ baud rate

DIP-No

3

2

0

0

Corresponding to P515 and P514 [32, 250kBaud]

0

1

Address 34, 250kBaud

1

0

Address 36, 250kBaud

1

1

Address 38, 250kBaud

3

2

2

BUS

Source control
word and setpoint
value

0

Corresponding to P509 and P510 [1] [2]

1

System bus (

P509=3 and P510=3)

NOTE

FACTORY SETTING, AS DELIVERED!

As delivered, all DIP switches are in the "0" ("off") position.

No.

Bit

DIP switch (S1)

3

2

2

U / I AIN2

Voltage/current

0

Analog input 2 in voltage mode 0...10 V

1

Analog input 2 in current mode 0/4...20 mA

2

2

1

U / I AIN1

Voltage/current

0

Analog input 1 in voltage mode 0...10 V

1

Analog input 1 in current mode 0/4...20 mA

1

2

0

SYS

Burden resistor

0

Burden resistor switched off

1

Burden resistor activated

S2

S1

AIN2

AIN1

SYS

ADR2

ADR1

BUS