Dip switch (s2), Dip switch (s1) – NORD Drivesystems BU0180 User Manual
Page 67
5 Commissioning
BU 0180 GB-0914
Pre-series version
67
5.2.2.2
DIP switch configuration of the inverter
The analog inputs in the frequency inverter are suitable for current and voltage setpoints. For correct
processing of current setpoints (0-20mA / 4-20mA) the relevant DIP switch (S1) must be set for current
signals ("ON").
Adjustment to fail-safe signals in case of cable breaks (2-10V/4-20mA) is made via parameters 402 and 403.
A second DIP switch (S2) is also available, via which the system bus address can be specified or the
system bus can be activated. This has priority over the parameters P509, P514 and P515.
No.
Bit
DIP switch (S2)
2/1
2
1/0
ADR
System bus
address/ baud rate
DIP-No
3
2
0
0
Corresponding to P515 and P514 [32, 250kBaud]
0
1
Address 34, 250kBaud
1
0
Address 36, 250kBaud
1
1
Address 38, 250kBaud
3
2
2
BUS
Source control
word and setpoint
value
0
Corresponding to P509 and P510 [1] [2]
1
System bus (
P509=3 and P510=3)
NOTE
FACTORY SETTING, AS DELIVERED!
As delivered, all DIP switches are in the "0" ("off") position.
No.
Bit
DIP switch (S1)
3
2
2
U / I AIN2
Voltage/current
0
Analog input 2 in voltage mode 0...10 V
1
Analog input 2 in current mode 0/4...20 mA
2
2
1
U / I AIN1
Voltage/current
0
Analog input 1 in voltage mode 0...10 V
1
Analog input 1 in current mode 0/4...20 mA
1
2
0
SYS
Burden resistor
0
Burden resistor switched off
1
Burden resistor activated
S2
S1
AIN2
AIN1
SYS
ADR2
ADR1
BUS