6 Parameterisation
BU 0180 GB-0914
Pre-series version
107
Parameter
{Factory setting}
Setting value / Description / Note
Device
Supervisor
Parameter
set
P475
[-01]
...
[-05]
delay on/off switch
(Switch on/off delay)
S
-30.000... 30,000 sec
{ 0.000 }
Adjustable on/off delay for the digital inputs. Use as a switch-on filter or simple process control
is possible.
[-01] = Digital input 1
[-02] = Digital input 2
[-03] = Digital input 3
[-04] = Digital input 4 / AIN1
[-05] = Digital input 5 / AIN2
Positive values = switch-on delayed
Negative values = switch-off delayed
P480
[-01]
...
[-12]
Funct. BusIO In Bits
(Function Bus I/O In Bits)
0 ... 77
{ [-01] = 01 }
{ [-02] = 02 }
{ [-03] = 05 }
{ [-04] = 12 }
{ [-05...-12] = 00 }
The Bus I/O In Bits are perceived as digital inputs. They can be set to the same functions
(P420).
These I/O bits can also be used in combination with the AS interface (SK 190) (Bit 0 … 3) or the
I/O extensions (SK xU4-
IOE) (Bit 4 … 7 and Bit 0 … 3).
[-01] = Bus / AS-i Dig In1
(Bus IO In Bit 0 + AS-i 1 or DI 1 of the second SK xU4-IOE (DigIn 09))
[-02] = Bus / AS-i Dig In2
(Bus IO In Bit 1 + AS-i 2 or DI 2 of the second SK xU4-IOE (DigIn 10))
[-03] = Bus / AS-i Dig In3
(Bus IO In Bit 2 + AS-i 3 or DI 3 of the second SK xU4-IOE (DigIn 11))
[-04] = Bus / AS-i Dig In4
(Bus IO In Bit 3 + AS-i 4 or. DI 4 of the second SK xU4-IOE (DigIn 12))
[-05] = Bus / IOE Dig In1
(Bus IO In Bit 4 + DI 1 of the first SK xU4-IOE (DigIn 05))
[-06] = Bus / IOE Dig In2
(Bus IO In Bit 5 + DI 2 of the first SK xU4-IOE (DigIn 06))
[-07] = Bus / IOE Dig In3
(Bus IO In Bit 6 + DI 3 of the first SK xU4-IOE (DigIn 07))
[-08] = Bus / IOE Dig In4
(Bus IO In Bit 7 + DI 4 of the first SK xU4-IOE (DigIN 08))
[-09] = Flag 1
[-10] = Flag 2
[-11] = Bit 8 BUS control word
[-12] = Bit 9 BUS control word
The possible functions for the bus In bits can be found in the table of functions for the digital
inputs in parameter (P420). Functions {14} "Remote control" and {29} "Enable SetpointBox" are
not possible.
NOTE: For AS-i devices (SK 190E), evaluation of a second IO extension is not possible.