6 Parameterisation

BU 0180 GB-0914

Pre-series version

107

Parameter

{Factory setting}

Setting value / Description / Note

Device

Supervisor

Parameter
set

P475

[-01]

...

[-05]

delay on/off switch

(Switch on/off delay)

S

-30.000... 30,000 sec

{ 0.000 }

Adjustable on/off delay for the digital inputs. Use as a switch-on filter or simple process control
is possible.

[-01] = Digital input 1

[-02] = Digital input 2

[-03] = Digital input 3

[-04] = Digital input 4 / AIN1

[-05] = Digital input 5 / AIN2

Positive values = switch-on delayed

Negative values = switch-off delayed

P480

[-01]

...

[-12]

Funct. BusIO In Bits

(Function Bus I/O In Bits)

0 ... 77

{ [-01] = 01 }

{ [-02] = 02 }

{ [-03] = 05 }

{ [-04] = 12 }

{ [-05...-12] = 00 }

The Bus I/O In Bits are perceived as digital inputs. They can be set to the same functions
(P420).

These I/O bits can also be used in combination with the AS interface (SK 190) (Bit 0 … 3) or the
I/O extensions (SK xU4-

IOE) (Bit 4 … 7 and Bit 0 … 3).

[-01] = Bus / AS-i Dig In1

(Bus IO In Bit 0 + AS-i 1 or DI 1 of the second SK xU4-IOE (DigIn 09))

[-02] = Bus / AS-i Dig In2

(Bus IO In Bit 1 + AS-i 2 or DI 2 of the second SK xU4-IOE (DigIn 10))

[-03] = Bus / AS-i Dig In3

(Bus IO In Bit 2 + AS-i 3 or DI 3 of the second SK xU4-IOE (DigIn 11))

[-04] = Bus / AS-i Dig In4

(Bus IO In Bit 3 + AS-i 4 or. DI 4 of the second SK xU4-IOE (DigIn 12))

[-05] = Bus / IOE Dig In1

(Bus IO In Bit 4 + DI 1 of the first SK xU4-IOE (DigIn 05))

[-06] = Bus / IOE Dig In2

(Bus IO In Bit 5 + DI 2 of the first SK xU4-IOE (DigIn 06))

[-07] = Bus / IOE Dig In3

(Bus IO In Bit 6 + DI 3 of the first SK xU4-IOE (DigIn 07))

[-08] = Bus / IOE Dig In4

(Bus IO In Bit 7 + DI 4 of the first SK xU4-IOE (DigIN 08))

[-09] = Flag 1

[-10] = Flag 2

[-11] = Bit 8 BUS control word

[-12] = Bit 9 BUS control word

The possible functions for the bus In bits can be found in the table of functions for the digital
inputs in parameter (P420). Functions {14} "Remote control" and {29} "Enable SetpointBox" are
not possible.

NOTE: For AS-i devices (SK 190E), evaluation of a second IO extension is not possible.