NORD Drivesystems BU0180 User Manual

Page 104

background image

SK 180E Manual for frequency inverters

104

Pre-series version

BU 0180 GB-0914

Parameter

{Factory setting}

Setting value / Description / Note

Device

Supervisor

Parameter
set

P434

[-01]

[-02]

Digital output function

(Digital output function)

0 ... 39

{ [-01] = 7 }

{ [-02] = 1 }

[-01] = Digital output 1, Digital output 1 of the frequency inverter

[-02] = Digital output 2, Digital output 2 of the frequency inverter

Control terminals 1/40 (Section 2.8.2 ): The settings 3 to 5 and 11 work with 10% hysteresis,
i.e. the relay contact closes (function 11 does not deliver) on reaching the limiting value 24 V
and switches this off again if a 10% lower value is undershot (function 11 on again).

This behaviour can be inverted with a negative value in P435.

Setting / Function

Output ...

with limiting

value or
function

(see also P435)

0 = No function

Low

1 = External brake, to control an external 24V brake relay (max. 20 mA).

The output switches at a programmed absolute minimum frequency
(P505).

For typical brakes a setpoint delay of 0.2-0.3 s should be programmed
(see also P107/P114).

High

2 = Inverter operating, the output indicates voltage at the FI output

(U - V - W)

.

High

3 = Current limit, based on the setting of the motor rated current (P203).

This value can be adjusted with the scaling (P435).

High

4 = Torque current limit, based on motor data settings in P203 and P206.

Signals a corresponding torque load on the motor. This value can be
adjusted with the standardisation (P435).

High

5 = Frequency limit, based on motor nominal frequency setting in P201.

This value can be adjusted with the scaling (P435).

High

6 = Setpoint reached, indicates that the FI has completed the frequency

increase or decrease. Setpoint frequency = actual frequency! From a
difference of 1 Hz  Setpoint value not achieved

– signal Low.

High

7 = Fault, general fault message, fault is active or not yet acknowledged.

Fault - Low (Ready - High)

Low

8 = Warning, general warning, a limit value was reached which could lead

to a later shutdown of the FI.

Low

9 = Overcurrent warning: At least 130% of the nominal FI current was

supplied for 30 seconds.

Low

10 = Overtemp. Warn. Motor, "Motor overtemperature warning": The motor

temperature is evaluated. Motor is too hot. The warning is given
immediately, overheating switch-off after 2 seconds.

Low

11 = Torque curr. lim. active, "Torque current limit / Current limit active

warning": The limiting value in P112 or P536 has been reached. A
negative value in P435 inverts the reaction. Hysteresis = 10%.

Low

12 = Value of P541, "Value of P541 -

external control“, the output can be

controlled with parameter P541 (Bit 0) independent of the actual
operating status of the FI.

High

13 = Gen. Torque limit,

"Generator torque limit active":Limit value in P112

has been reached in the generator range. Hysteresis = 10%.

High

16 = Reference value Ain1,

Setpoint AIN1 of the FI is compared with the value in (P435[-01 or -02]).

High

17 = Reference value Ain2,

Setpoint AIN2 of the FI is compared with the value in (P435[-01 or -02]).

High