8 technical data – NORD Drivesystems BU0180 User Manual
Page 151
8 Technical data
BU 0180 GB-0914
Pre-series version
151
8 Technical data
8.1 General data for frequency inverter series SK 1x0E
Function
Specification
Output frequency
0.0 … 400.0 Hz
Pulse frequency
3.0 … 16.0 kHz, standard setting = 6 kHz
Power reduction > 8 kHz for 115/230V device, >6 kHz for 400 V device.
Typical overload capacity
150% for 60 s, 200% for 3.5 s
Protection measures against
Overtemperature of the frequency inverter,
overvoltage and undervoltage
Short-circuit, earthing fault,
overload, idling
Regulation and control
Sensorless current vector control (ISD), linear V/f characteristic curve,
automatic flux adaptation (energy-saving function)
Motor temperature monitoring
I
2
t motor, PTC / Bimetal switch
Digital input
3x low 0-5 V, high 14-30 V, R
i
= 9.5 k
, C
i
= 10 nF, cycle time = 4 ms
Electrical isolation
Control terminals
Control outputs
digital output: 24V±25% DC, max. 20mA, max. 1.2k
Load
Interfaces
Standard: RS 485 (USS)
– only for
Parameter boxes
RS 232 (Single Slave)
System bus
Option: Profibus, CANopen,
DeviceNet, AS-Interface,
EtherCAT, PROFINET,
POWERLINK,
Ethernet/IP
Efficiency of frequency inverter
> 95% according to size
Storage and transport temperature
-
25°C … +60/70°C
Operating / ambient temperature
-
25°C … +50°C, according to operating mode (Details: Section 8.2)
ATEX: -
20…+40°C (Details: Section 2.10)
Long-term storage
See Section 9.11.1
Protection class
IP55, optional IP66
Max. installation altitude above sea
level
Up to 1000 m: No power reduction
1000...4000 m: 1%/ 100 m power reduction (up to 2000m overvoltage cat. 3)
2000...4000 m: Only overvoltage category 2 is maintained, external
overvoltage protection at the mains input is necessary
Ambient conditions
Transport (IEC 60721-3-2):
Vibration: 2M2
Operation (IEC 60721-3-3):
Vibration: 3M7;
Climate: 3K3 (IP55)
/ 3K4 (IP66)
Waiting time between
two mains switching cycles
60 sec for all devices in normal operating cycle
Mains/motor/brake resistance
4mm
2
flexible cable with wire end sleeves,
6mm
2
with rigid cable
Terminal screw
tightening torque
0.5...0.6 Nm
Control unit /System bus
1.5mm
2
, rigid and flexible cable with wire end
sleeves, 0.75mm² flexible cable with wire end sleeves
with plastic sleeves
RS485 / RS232
1x RJ12 (6-pin)
24V - Output
(Terminal 43)
Digital outputs
24 V DC ± 25%, max. 150 mA
3
24 V DC ± 25%, max. 20 mA
3
The current which is drawn from the digital outputs must also be covered by this. Any control modules which are
connected to the RJ12 socket also place a load on the 24V supply. (150mA = I
DIG1
+ I
DIG2
+ I
OUT
+ I
CONTROL
)