NORD Drivesystems BU0180 User Manual
Page 105
6 Parameterisation
BU 0180 GB-0914
Pre-series version
105
Parameter
{Factory setting}
Setting value / Description / Note
Device
Supervisor
Parameter
set
18 = FI ready: The FI is ready for operation. After being enabled it delivers
an output signal.
High
19 = ... 29 reserved
30 = Digital-In 1 status*
High
Details for the
use of the
relevant bus
systems can be
found in the
applicable
supplementary
bus manual.
31 = Digital-In 2 status*
High
32 = Digital-In 3 status*
High
33 = Status Digital-In 4 / A-In1 *
High
34 = Status Digital-In 5 / A-In2 *
*) (P546[-
01]…[-03]) = 20
P435
[-01]
[-02]
Dig. out scaling
(Scaling of digital output)
-400 ... 400 %
{ 100 }
[-01] =
Digital output 1, Digital output 1 of the frequency inverter
[-02] =
Digital output 2, Digital output 2 of the frequency inverter
Adjustment of the limiting values of the output function. For a negative value, the output function
will be output negative.
Reference to the following values:
Current limit (3) = x [%]
P203 >Rated motor current<
Torque current limit (4) = x [%]
P203
P206 (calculated rated motor torque)
Frequency limit (5) = x [%]
P201 >Rated motor frequency<
P436
[-01]
[-02]
Dig. out. hysteresis
(Hysteresis of digital outputs)
S
1 ... 100 %
{ 10 }
[-01] =
Digital output 1, Digital output 1 of the frequency inverter
[-02] =
Digital output 2, Digital output 2 of the frequency inverter
Difference between switch-on and switch-off point to prevent oscillation of the output signal.
P460
Time watchdog
(Time watchdog)
S
0.0 / 0.1 ... 250.0 s
-0.1 ... -250.0 sec
{ 10.0 }
0.1 ... 250.0 = The time interval between the expected Watchdog signals (programmable
function of the digital inputs P420
– P425). If this time interval passes without a
pulse being registered, a switch off occurs with an E012 error message.
0.0 = Customer error: As soon as a high-low flank or a low signal is detected at a digital input
(function 18) the FI switches off with error message E012.
-0.1 ... -250.0 =
In this case the rotor rotation watchdog is active The time is defined by the
amount of the set value. There is no watchdog message when switched off.
After each enable, a puls must first come before the watchdog is activated.