Display in the
SimpleBox
Fault
Text in the ParameterBox
Cause
Remedy
Group
Details in
P700[-01] /
P701
E010
10.0
Bus Timeout
(Telegram time-out /
Bus off 24V int. CANbus)
Data transfer is faulty. Check P513.
Check physical bus connections.
Check bus protocol program process.
Check Bus Master.
Check 24V supply of internal CAN/CANopen Bus.
Nodeguarding error (internal CANopen)
Bus Off error (internal CANbus)
10.2
Bus Timeout Option
(Telegram timeout)
Telegram transfer is faulty.
Check physical connections.
Check bus protocol program process.
Check Bus Master.
10.4
Init error Option
(Initialisation error in bus
module)
Check Bus module current supply.
DIP switch setting of a connected I/O extension module is
incorrect
10.1
System error option
(Bus module)
Further details can be found in the respective additional
BUS operating instructions.
I/O extension:
Incorrect measurement of the input voltage or undefined
provision of the output voltage due to error in reference
voltage generation.
Short circuit at analog output
10.3
10.5
10.6
10.7
10.9
Module missing / P120
The module entered in parameter (P120) is not available.
E011
11.0
Customer interface
(AnalogDigital converter error)
Internal customer unit (internal databus) faulty or damaged
by radio radiation (EMC)
Check control terminals connection for short-circuit.
Minimize EMC interference by laying control and power
cables separately.
Device and shielding must be well earthed.