3.12 Measuring Power (/PWR1 Option)
Power Monitor Function
Measure the measurement elements of electrical power. Set an expression on a
computation channel, and then start the computation to begin the measurement.
In addition, by using other operators, you can measure the maximum, minimum, average
and electric energy.
Measurement Element
Symbol
Description
Active or regenerative power
WAT
Power values without the low-cut
function applied.
Active power
WATP
Regenerative power
WATN
Reactive power
VAR
Reactive power (LAG)
VARP
Reactive power (LEAD)
VARN
Apparent power
VA
Active or regenerative power (low-cut)
_WAT_
Power values with the low-cut
function applied. The electric energy
is measured by summing these
measurement elements.
The low-cut function sets the
measured value to 0 when the
measured value is less than the set
low-cut power. With no load, this
function prevents the influence of noise
present in each measurement element
from accumulating in the power
consumption (Wh) calculation.
Active power (low-cut)
_WATP_
Regenerative power (low-cut)
_WATN_
Reactive power (low-cut)
_VAR_
Reactive power (LAG; low-cut)
_VARP_
Reactive power (LEAD; low-cut)
_VARN_
Apparent power (low-cut)
_VA_
Voltage (V1)
VOL1
This is the voltage.
Voltage (V2)
VOL2
This is the voltage. This is only valid
for single-phase three-wire systems.
Voltage (V3)
VOL3
This is the voltage. This is only valid
for three-phase three-wire systems.
Current (I1)
CUR1
This is the current.
Current (I2)
CUR2
This is the current. This is only valid for
single-phase three-wire systems.
Current (I3)
CUR3
This is the current. This is only valid for
three-phase three-wire systems.
Frequency
HZ
This is the frequency.
Power factor
PF
This is the power factor.
Measuring Electric Energy
The electric energy is calculated by summing the measured values of the power
measurement channels. To avoid the influence of noise in this calculation, normally use
the low-cut function. On the FX, sum powers to which the low-cut function has been
applied (_WAT_, _WATP_, _WATN_, _VAR_, _VARP_, _VARN_, and _VA_ in the above
table) to measure the electric energy. You can set the low-cut point to any value that you
want.
• Computation Channels
You can write expressions in computation channels to measure the electric energy.
You have to set an expression—one which will be used to sum the measured power
values—in a computation channel. The sum is set using the TLOG expression and
the timer (see example 4 in this section). The TLOG expressions are shown in the
following table.