App index – Yokogawa Value Series FX1000 User Manual
Page 292
14-5
IM 04L21B01-01EN
Setup Items
3
2
1
4
5
6
7
8
9
10
11
12
13
14
App
Index
Setup Item
Selectable Range or Selections
Default Value Setting
Mode = DI
Range
Level/Cont
Level
Span Lower
Numerical value (0 or 1)
0
Span Upper
Numerical value (0 or 1)
1
Mode = 1-5V
Range
1-5V
1-5V
Span Lower
Numerical value (0.800 to 5.200)
1.000
Span Upper
Numerical value (0.800 to 5.200)
5.000
Scale Lower
Numerical value (–30000 to 30000; decimal place: 0 to 4)
0.00
Scale Upper
Numerical value (–30000 to 30000)
200.00
Unit
6 characters or less
−
Low-cut
On/Off
Off
Mode = Sqrt
Range
20mV/60mV/200mV/2V/6V/20V/50V/1V
Span Lower
Numerical value (depends on the range)
−
Span Upper
Numerical value (depends on the range)
−
Scale Lower
Numerical value (–30000 to 30000; decimal place: 0 to 4)
0.00
Scale Upper
Numerical value (–30000 to 30000)
200.00
Unit
6 characters or less
−
Low-cut
On/Off
Off
Low-cut value
Numerical value (0.0 to 5.0)
0.5
Mode = LogType1
Range
20mV/60mV/200mV/2V/6V/20V/50V/1V
2V
Span Lower
Numerical value (depends on the range)
–2.0000
Span Upper
Numerical value (depends on the range)
2.0000
Scale Lower
Mantissa (1.00 to 9.99) and exponent (–15 to 15)
2.00E0
Scale Upper
Mantissa (1.00 to 9.99) and exponent (–15 to 15)
2.00E14
Unit
6 characters or less
−
Mode = LogType2
Range
20mV/60mV/200mV/2V/6V/20V/50V/1V
2V
Span Lower
Numerical value (depends on the range)
–2.0000
Span Upper
Numerical value (depends on the range)
2.0000
Scale Lower
Mantissa (1.00 to 9.99) and exponent (–15 to 15)
2.00E0
Scale Upper
Mantissa (automatically set to the same value as Scale Lower)
and exponent (–15 to 15)
−
Unit
6 characters or less
−
Alarm
1, 2, 3, 4
On/Off
Off
Type
H: High/L: Low/h: delta H/l: delta L/
H
R: rate H/r: rate L/T: delay H/t: delay L
Value
Numerical value
When Mode is LogType, this is set with the mantissa and the
exponent.
The range is 1.00E–16 to 1.00E+16 (the mantissa range is 1.00
to 9.99)
−
Relay
On/Off
Off
Number
I01/I02/. . . /I06, I11/I12/. . . /I16 (depends on the options)
I01
S01/S02/S03/. . . /S29/S30
Detect
On/Off
On
Meas channel > Tag, Memory, Delay
Setup Item
Selectable Range or Selections
Default Value Setting
First-CH, Last-CH
Channel number
001
Tag > Characters
16 characters or less
−
Memory sample > On/Off
On/Off
On
Alarm delay > Time
Numerical value (1 to 3600; in seconds)
10
Meas channel > Moving average
Setup Item
Selectable Range or Selections
Default Value Setting
First-CH, Last-CH
Channel number
001
On/Off
On/Off
Off
Count
Numerical value (2 to 400)
2
14.1 Setting Mode Menu Map and Setup Items