beautypg.com

App index – Yokogawa Value Series FX1000 User Manual

Page 292

background image

14-5

IM 04L21B01-01EN

Setup Items

3

2

1

4

5

6

7

8

9

10

11

12

13

14

App

Index

Setup Item

Selectable Range or Selections

Default Value Setting

Mode = DI

Range

Level/Cont

Level

Span Lower

Numerical value (0 or 1)

0

Span Upper

Numerical value (0 or 1)

1

Mode = 1-5V

Range

1-5V

1-5V

Span Lower

Numerical value (0.800 to 5.200)

1.000

Span Upper

Numerical value (0.800 to 5.200)

5.000

Scale Lower

Numerical value (–30000 to 30000; decimal place: 0 to 4)

0.00

Scale Upper

Numerical value (–30000 to 30000)

200.00

Unit

6 characters or less

Low-cut

On/Off

Off

Mode = Sqrt

Range

20mV/60mV/200mV/2V/6V/20V/50V/1V

Span Lower

Numerical value (depends on the range)

Span Upper

Numerical value (depends on the range)

Scale Lower

Numerical value (–30000 to 30000; decimal place: 0 to 4)

0.00

Scale Upper

Numerical value (–30000 to 30000)

200.00

Unit

6 characters or less

Low-cut

On/Off

Off

Low-cut value

Numerical value (0.0 to 5.0)

0.5

Mode = LogType1

Range

20mV/60mV/200mV/2V/6V/20V/50V/1V

2V

Span Lower

Numerical value (depends on the range)

–2.0000

Span Upper

Numerical value (depends on the range)

2.0000

Scale Lower

Mantissa (1.00 to 9.99) and exponent (–15 to 15)

2.00E0

Scale Upper

Mantissa (1.00 to 9.99) and exponent (–15 to 15)

2.00E14

Unit

6 characters or less

Mode = LogType2

Range

20mV/60mV/200mV/2V/6V/20V/50V/1V

2V

Span Lower

Numerical value (depends on the range)

–2.0000

Span Upper

Numerical value (depends on the range)

2.0000

Scale Lower

Mantissa (1.00 to 9.99) and exponent (–15 to 15)

2.00E0

Scale Upper

Mantissa (automatically set to the same value as Scale Lower)

and exponent (–15 to 15)

Unit

6 characters or less

Alarm

1, 2, 3, 4

On/Off

Off

Type

H: High/L: Low/h: delta H/l: delta L/

H

R: rate H/r: rate L/T: delay H/t: delay L

Value

Numerical value

When Mode is LogType, this is set with the mantissa and the

exponent.

The range is 1.00E–16 to 1.00E+16 (the mantissa range is 1.00

to 9.99)

Relay

On/Off

Off

Number

I01/I02/. . . /I06, I11/I12/. . . /I16 (depends on the options)

I01

S01/S02/S03/. . . /S29/S30

Detect

On/Off

On

Meas channel > Tag, Memory, Delay

Setup Item

Selectable Range or Selections

Default Value Setting

First-CH, Last-CH

Channel number

001

Tag > Characters

16 characters or less

Memory sample > On/Off

On/Off

On

Alarm delay > Time

Numerical value (1 to 3600; in seconds)

10

Meas channel > Moving average

Setup Item

Selectable Range or Selections

Default Value Setting

First-CH, Last-CH

Channel number

001

On/Off

On/Off

Off

Count

Numerical value (2 to 400)

2

14.1 Setting Mode Menu Map and Setup Items