Power Monitor (/PWR1)

Unless otherwise specified, the performance values listed here were recorded under the following standard operating conditions:

23 ± 2°C, 55 ± 10%RH; power supply frequency: 50/60 Hz ± 1% or less; rated input: ±1% or less, power factor: 1 ± 1% or less;

warm-up time: 30 minutes or more; and a location in which oscillations and other factors do not affect the operation of the

instrument.

Item

Specifications

Measurement element

By including power measurement elements in an expression, you can measure a variety of power

values.

Active power, regenerative electric power, reactive power, apparent power, voltage, current,

frequency, power factor (LEAD: –, LAG: +), and

electric energy (active energy, regenerative energy, reactive energy—LAG: +, reactive energy—

LEAD: —, and apparent energy)

* The LEAD/LAG sign is calculated from the phase difference between P1 (voltage) and I1

(current).

Phase and wiring system

Single-phase two-wire system, single-phase three-wire system, and three-phase three-wire system

Frequency

45 to 65 Hz

Rated input voltage

Rated Voltage Voltage Range (Variable)

Allowable Input Voltage

Crest

Factor
120 V 120 V

150 V

2

240 V 240 V

300 V

2

Rated input current

Rated Current Current Range (Fixed)

Allowable Input Current

Crest

Factor
1 A 1 A

1.2 A

2

Allowable input range

150 Vrms (when the voltage range is set to 120 V), 300 Vrms (when the voltage range is set to 240 V),

and 1.2 A (when using current input)

Rated input power and measuring range

Single-phase two-wire system

Input (AC)

Input Measuring Range

1

Approximate Consumed VA

Rated Power

Voltage

Current

120 V/1 A

100 W

–120 to 120 W

0.2 VA

0.2 VA

240 V/1 A

200 W

–240 to 240 W

0.4 VA

Single-phase three-wire system

Input (AC)

Input Measuring Range Approximate Consumed VA

Rated Power

Voltage

Current

200 V/1 A

200 W

–240 to 240 W

0.2 VA/phase 0.2 VA/phase

Three-phase three-wire system

Input (AC)

Input Measuring Range Approximate Consumed VA

Rated Power

Voltage

Current

120 V/1 A

200 W

–240 to 240 W

0.2 VA/phase

0.2 VA/phase

240 V/1 A

400 W

–480 to 480 W

0.4 VA/phase

The input measuring range when you are using a VT and CT is calculated using the following

equation. The measuring range must be within the input measuring ranges listed above, and the

primary side input power

2

must be less than 10 GW.

1 Input measuring range (W) = Primary side input power

2

in W/(VT ratio × CT ratio).

2 Primary side input power = Secondary side rated power in W Ч 1.2 Ч VT ratio × CT ratio.

Measuring range

Power factor: (LEAD) 0.5 to 1 to (LAG) 0.5

Frequency: 45 to 65 Hz

13.5 Options