Yokogawa Value Series FX1000 User Manual
Page 180
6-11
IM 04L21B01-01EN
Saving and Loading Data
3
2
1
4
5
6
7
8
9
10
11
12
13
14
App
Index
• Stopping the Recording (Memory Stop)
1.
Press
STOP. A confirmation window is displayed.
If you are using the batch function, the batch name and comment are displayed
on the screen.
2.
Select
Yes using the arrow keys and press DISP/ENTER.
If the FX is equipped with computation functions (/M1, /PM1, and /PWR1
options), select
Mem+Math or Memory, and then press DISP/ENTER.
The internal memory icon in the status display section changes to the stop icon.
• Saving the Data in the Internal Memory Collectively or Selectively
through Key Operation
See section 4.8.
Explanation
• Operations That Start Simultaneously with Memory Start
• Waveform display updating on the trend display.
• Report (/M1, /PM1, and /PWR1 options)
• The computation function (/M1, /PM1, and /PWR1 options) can be configured to
start simultaneously with memory start.
See section 9.4.
• Operations That Stop Simultaneously with Memory Stop
• Waveform display updating on the trend display.
• Report (/M1, /PM1, and /PWR1 options)
• Computation function (/M1, /PM1, and /PWR1 options): When selected in the
procedure described above.
• Performance While Data Is Being Saved
If the internal memory or external storage medium is continuously accessed, the
following phenomena may occur.
• Files being saved to the external storage medium drop out.
• Accessing the FX through communications takes a long time
In such case, take the following measures.
• If you are creating data files at short intervals consecutively using the event action
function, increase the data file save interval.
• If you are creating numerous files in a single directory on the external storage
medium, change the destination directory name at approximately every 1000 files.