App index fail/status output relay (/f1), Wire isolated rtd input (/n2) – Yokogawa Value Series FX1000 User Manual
Page 276
13-11
IM 04L21B01-01EN
Specifications
3
2
1
4
5
6
7
8
9
10
11
12
13
14
App
Index
FAIL/Status Output Relay (/F1)
Item
Specifications
FAIL output
Relay contact output on CPU error
Relay operation
Energized during normal operation and de-energized on system error.
Status output
Output a relay contact signal when a selected condition occurs.
A combination of the following conditions can be selected:
Low memory, memory failure, media error, A/D hardware error, burnout detection, communication
error (Modbus master or client communication error), memory sampling stop.
Relay operation
Relay is energized when a condition occurs.
Relay contact rating
250 VAC (50/60 Hz)/3 A, 250 VDC/0.1 A (for resistance load)
Computation Function (including the report function) (/M1)
Item
Specifications
Number of computation channels
FX1002 and FX1004: 12 channels (101 to 112)
FX1006, FX1008, FX1010, and FX1012: 24 channels (101 to 124)
Operation
General arithmetic operations: Four arithmetic operations, square root, absolute, common logarithm,
natural logarithm, exponential, and power
Relational operations:
<, ≤, >, ≥, =, and ≠
Logic operations:
AND, OR, NOT, and XOR
Statistical operations:
TLOG and CLOG
Special operations:
PRE, HOLD, RESET, and CARRY
Conditional operation:
[a?b:c]
Computation accuracy
Double-precision floating point
Data that can be used
Channel data
Measurement and computation channels
Constants
60 constants
Communication input data 24
Remote control input status 0/1 (/R1)
Pulse input
Counts the number of pulses (/PM1)
Status input
Internal switch, alarm output relay (/A[ ] and /A4A), flags
Rolling average
Performs moving average on the computed results.
Measurement range
–9999999 to 99999999
Decimal place: 0 to 4 digits to the right of the decimal point
Unit
Up to 6 characters in length
Sum scales: Off, /s, /min, /h, /day
Alarms
High limit, low limit, delay high limit, and delay low limit
Hysteresis: High and low limit alarm: 0.0% to 5.0% of the span.
Display
Same as the measurement channels
Data saving
Same as the measurement channels
Report function
Number of report channels: 12 or 24 (same as the number of computation channels)
Computation types: Average, maximum, minimum, sum, or instantaneous value
Report types: Hourly, daily, hourly + daily, daily + weekly, daily + monthly
3-Wire Isolated RTD Input (/N2)
Item
Specifications
Input terminal
All the RTD input terminals (A, B, and b) are isolated on each channel.
Applies to the FX1006, FX1008, FX1010, and FX1012
Note: On the FX1002 and FX1004 standard models, the A, B, and b terminals are already isolated
on each channel.
13.5 Options