beautypg.com

App index fail/status output relay (/f1), Wire isolated rtd input (/n2) – Yokogawa Value Series FX1000 User Manual

Page 276

background image

13-11

IM 04L21B01-01EN

Specifications

3

2

1

4

5

6

7

8

9

10

11

12

13

14

App

Index

FAIL/Status Output Relay (/F1)

Item

Specifications

FAIL output

Relay contact output on CPU error

Relay operation

Energized during normal operation and de-energized on system error.

Status output

Output a relay contact signal when a selected condition occurs.

A combination of the following conditions can be selected:

Low memory, memory failure, media error, A/D hardware error, burnout detection, communication

error (Modbus master or client communication error), memory sampling stop.

Relay operation

Relay is energized when a condition occurs.

Relay contact rating

250 VAC (50/60 Hz)/3 A, 250 VDC/0.1 A (for resistance load)

Computation Function (including the report function) (/M1)

Item

Specifications

Number of computation channels

FX1002 and FX1004: 12 channels (101 to 112)

FX1006, FX1008, FX1010, and FX1012: 24 channels (101 to 124)

Operation

General arithmetic operations: Four arithmetic operations, square root, absolute, common logarithm,

natural logarithm, exponential, and power

Relational operations:

<, ≤, >, ≥, =, and ≠

Logic operations:

AND, OR, NOT, and XOR

Statistical operations:

TLOG and CLOG

Special operations:

PRE, HOLD, RESET, and CARRY

Conditional operation:

[a?b:c]

Computation accuracy

Double-precision floating point

Data that can be used

Channel data

Measurement and computation channels

Constants

60 constants

Communication input data 24

Remote control input status 0/1 (/R1)

Pulse input

Counts the number of pulses (/PM1)

Status input

Internal switch, alarm output relay (/A[ ] and /A4A), flags

Rolling average

Performs moving average on the computed results.

Measurement range

–9999999 to 99999999

Decimal place: 0 to 4 digits to the right of the decimal point

Unit

Up to 6 characters in length

Sum scales: Off, /s, /min, /h, /day

Alarms

High limit, low limit, delay high limit, and delay low limit

Hysteresis: High and low limit alarm: 0.0% to 5.0% of the span.

Display

Same as the measurement channels

Data saving

Same as the measurement channels

Report function

Number of report channels: 12 or 24 (same as the number of computation channels)

Computation types: Average, maximum, minimum, sum, or instantaneous value

Report types: Hourly, daily, hourly + daily, daily + weekly, daily + monthly

3-Wire Isolated RTD Input (/N2)

Item

Specifications

Input terminal

All the RTD input terminals (A, B, and b) are isolated on each channel.

Applies to the FX1006, FX1008, FX1010, and FX1012

Note: On the FX1002 and FX1004 standard models, the A, B, and b terminals are already isolated

on each channel.

13.5 Options