• Range > Type

Input type when

Mode is Delta or Scale. See the description on Mode above.

• Range > Range

Input type details.

Setting

Input Type

Notes

Setting Input Type

Notes

20mV

–20.000 mV to 20.000 mVDC Standard

R

Type R

Standard

60mV

–60.00 mV to 60.00 mVDC

S

Type S

200mV

–200.00 mV to 200.00 mVDC

B

Type B

1V

–1.0000 V to 1.0000 VDC

K

Type K

2V

–2.0000 V to 2.0000 VDC

E

Type E

6V

–6.000 V to 6.000 VDC

J

Type J

20V

–20.000 V to 20.000 VDC

T

Type T

50V

–50.00 V to 50.00 VDC

N

Type N

Pt

Pt100

W

Type W

JPt

JPt100

L

Type L

Level

On/off (voltage)

U

Type U

Contact

On/off (contact)

WRe

Type WRe

1-5V

0.800 V to 5.200 V

Setting

Input Type

Notes

Kp

Kp vs Au7Fe

/N3F

option

PLATI

PLATINEL

PR

PR40-20

NiMo

NiNiMo

W/WRe

W/WRe26

N2

Type N (AWG14)

XK

XK GOST

Ni1

Ni100 (SAMA)

Ni2

Ni100 (DIN)

Ni3

Ni120

Pt100G

Pt100 GOST

Cu100G

Cu100 GOST

Cu50G

Cu50 GOST

Pt200W

Pt200 (WEED)

• Range > Span_L, Span_U

Input range. The selectable range is displayed on the screen.

Note

• You cannot set the same value to

Span_L and Span_U.

• When the

Mode is 1-5V or Sqrt, Span_L must be less than Span_U.

• Range > Scale_L, Scale_U

Input range after converting the unit.
The selectable range is from –30000 to 30000. The decimal place is determined by

the

Scale_L setting. It can be set to the following positions: “X.XXXX,” “XX.XXX,” “XXX.

XX,” “XXXX.X,” or “XXXXX.”

Note

• The FX converts the measured value to a value within the range set by the

Scale_L and

Scale_U values with their decimal points removed. For example, if the scale setting is
“–5 to 5,” the value is converted to a value within the span of “10”; if the scale setting is “–5.0
to 5.0,” the value is converted to a value within a span of “100.” In this case, the resolution
of the value converted to a span of “10” is lower than the value converted to a span of “100.”
To prevent the display from becoming rough, it is recommended that the scale be set so that
this value is greater than 100.

• You cannot set the same value to

Scale_L and Scale_U.

• When the

Mode is 1-5V or Sqrt, Scale_L must be less than Scale_U.