Measurement Channels and
Alarms
IM 04L21B01-01EN
3-5
3
2
1
4
5
6
7
8
9
10
11
12
13
14
App
Index
• Range > Type
Input type when
Mode is Delta or Scale. See the description on Mode above.
• Range > Range
Input type details.
Setting
Input Type
Notes
Setting Input Type
Notes
20mV
–20.000 mV to 20.000 mVDC Standard
R
Type R
Standard
60mV
–60.00 mV to 60.00 mVDC
S
Type S
200mV
–200.00 mV to 200.00 mVDC
B
Type B
1V
–1.0000 V to 1.0000 VDC
K
Type K
2V
–2.0000 V to 2.0000 VDC
E
Type E
6V
–6.000 V to 6.000 VDC
J
Type J
20V
–20.000 V to 20.000 VDC
T
Type T
50V
–50.00 V to 50.00 VDC
N
Type N
Pt
Pt100
W
Type W
JPt
JPt100
L
Type L
Level
On/off (voltage)
U
Type U
Contact
On/off (contact)
WRe
Type WRe
1-5V
0.800 V to 5.200 V
Setting
Input Type
Notes
Kp
Kp vs Au7Fe
/N3F
option
PLATI
PLATINEL
PR
PR40-20
NiMo
NiNiMo
W/WRe
W/WRe26
N2
Type N (AWG14)
XK
XK GOST
Ni1
Ni100 (SAMA)
Ni2
Ni100 (DIN)
Ni3
Ni120
Pt100G
Pt100 GOST
Cu100G
Cu100 GOST
Cu50G
Cu50 GOST
Pt200W
Pt200 (WEED)
• Range > Span_L, Span_U
Input range. The selectable range is displayed on the screen.
Note
• You cannot set the same value to
Span_L and Span_U.
• When the
Mode is 1-5V or Sqrt, Span_L must be less than Span_U.
• Range > Scale_L, Scale_U
Input range after converting the unit.
The selectable range is from –30000 to 30000. The decimal place is determined by
the
Scale_L setting. It can be set to the following positions: “X.XXXX,” “XX.XXX,” “XXX.
XX,” “XXXX.X,” or “XXXXX.”
Note
• The FX converts the measured value to a value within the range set by the
Scale_L and
Scale_U values with their decimal points removed. For example, if the scale setting is
“–5 to 5,” the value is converted to a value within the span of “10”; if the scale setting is “–5.0
to 5.0,” the value is converted to a value within a span of “100.” In this case, the resolution
of the value converted to a span of “10” is lower than the value converted to a span of “100.”
To prevent the display from becoming rough, it is recommended that the scale be set so that
this value is greater than 100.
• You cannot set the same value to
Scale_L and Scale_U.
• When the
Mode is 1-5V or Sqrt, Scale_L must be less than Scale_U.
3.3 Setting the Input Range