beautypg.com

9 fail/status output function (/f1 option), 9 fail/status output function (/f1 option) -47, App index – Yokogawa Value Series FX1000 User Manual

Page 56: Fail output, Status output

background image

1-47

IM 04L21B01-01EN

Overview of Functions

3

2

1

4

5

6

7

8

9

10

11

12

13

14

App

Index

1.9 FAIL/Status Output Function (/F1 Option)

FAIL Output

When a failure occurs in the FX CPU, the FX generates a relay contact signal (1 signal).
The relay is energized when the CPU is normal and de-energizes when a CPU failure
occurs. Therefore, relay output is carried out also when the power is turned OFF (including
a power failure). You cannot change this behavior.

Relay Operation

NO

C

NC

During normal operation

NO

C

NC

When a failure occurs

NO

C

NC

When power is turned OFF

If a failure occurs, contact your nearest YOKOGAWA dealer.

Status Output

Outputs the status below with a relay contact signal (1 relay). The relay is energized
when the status occurs. You cannot change this behavior.
For the setting procedure, see section 2.9.

Status

Description

Corrective Action

Status of the internal
memory or CF card

Error in the internal memory.

Contact your nearest YOKOGAWA

dealer.

When the auto save function to the CF card is On.

• The free space on the CF card dropped

to 10% of the total size (only when

the media FIFO (see section 1.4) is

disabled).

Replace the CF card.

• Error in the CF card.

• Replace the CF card with a

normal one.

• Use the FX to format the CF

card (the CF card data will be

deleted).

However, the status of the internal memory

is output when the CF card is not inserted.
• 10 MB or less of available space*

remaining in internal memory.

• The number of files in internal memory

for which Auto Save to the CF card has

not been completed has exceeded 390.

Insert a CF card.

When the auto save function to the CF card is Off.

• 10 MB or less of available space*

remaining in internal memory.

• The number of files in internal memory

for which Manual Save has not been

completed has exceeded 390.

Save the data in the internal

memory to the CF card.

Measurement error

Error in the A/D converter.

Contact your nearest YOKOGAWA

dealer.

Burnout is detected.

Replace the thermocouple that

has burned out.

Communication error A Modbus master or Modbus client

communication error occurred.

Check the error in the Modbus

master or Modbus client screen

and carry out the corrective action.

Memory stop

When the memory sampling is stopped.

Start the data acquisition.

* The internal memory’s “available space” refers to the following quantities.
• Unused regions
• Regions of data for which Auto Save or Manual Save (see page 1-28) has been

completed.