6-3

IM 04L21B01-01EN

Saving and Loading Data

3

2

1

4

5

6

7

8

9

10

11

12

13

14

App

Index

• Event data (when recording event data)

• Sample rate

Select the data recording interval. Use the table under “Data length” for reference.

• Mode

Settings

Description

Free

Records data continuously.

Single

Records data when the trigger condition is met.

Repeat

Records data each time the trigger condition is met.

• Data length

Select the size of a record data file. The recorded data is divided by the file size

specified here. The available data lengths vary depending on the number of
memory sampling channels and the

Sample rate setting.

Sample rate

1

125 ms

250 ms

500 ms

1 s

2 s

Selectable range

of data length

10 min to

1 day

10 min to

2 days

10 min to

3 days

10 min to

7 days

10 min to

14 days

Sample rate

1

5 s

10 s

30 s

1 min

2 min

Selectable range

of data length

10 min to

31 days

10 min to

31 days

1 hour to

31 days

1 hour to

31 days

1 hour to

31 days

Sample rate

1

5 min

10 min

Selectable range

of data length

1 hour to

31 days

1 hour to

31 days

1 You cannot choose a sample rate that is higher than the scan interval.

• Pre-trigger

Specify the range when recording data before the trigger condition is met. Select

the range as a percentage of the data length from

0, 5, 25, 50, 75, 95, and 100%.

If you do not want to record the data existing before the trigger condition is met,
select

0%.

• Trigger signal > Key

Select

On if you want to activate the trigger using key operation.

Note

• Triggers can be applied using event action (see section 7.1).
• If the trigger condition is already met when you press START, recording starts.

6.1 Setting the Recording Conditions of the Measured Data