14-10

IM 04L21B01-01EN

Timer, Event action > Event action

Setup Item

Selectable Range or Selections

Default Value Setting

Logic box number

Numerical value (1 to 40)

1

Event

None/Remote/Relay/Switch/Timer/Match time timer/

Alarm/UserKey

None

Remote > Remote number

1/2/3/4/5/6/7/8

1

Relay > Relay number

I01/I02/. . . /I06, I11/I12/. . . /I16 (depends on the

options)

I01

Switch > Switch No.

S01/S02/S03/. . . /S29/S30

S01

Timer > Timer No.

1/2/3/4

1

Match time timer > Timer number

1/2/3/4

1

Action

MemoryStart/Stop, MemoryStart, MemoryStop,

Trigger, AlarmACK, MathStart/Stop, MathStart,

MathStop, MathReset, SaveDisplay, SaveEvent,

Message, Snapshot, DisplayRate1/2,

ManualSample, TimerReset, DisplayGroupChange,

Flag, PanelLoad, TimeAdjust (depends on settings

such as the event settings)

DisplayGroup
Change

Message > Message No.

Numerical value (1 to 100)

1

Message > Write to

All/Select

All

Message > Group number

1/2/3/4/5/6/7/8/9/10

1

Group > Group number

1/2/3/4/5/6/7/8/9/10

1

Flag > Flag number

1/2/3/4/5/6/7/8

1

TimerReset > Timer No.

1/2/3/4

1

PanelLoad > Setting file number

1/2/3

1

Data save > File header, File name

Setup Item

Selectable Range or Selections

Default Value Setting

File header > Characters

50 characters or less

Data file name > Structure

Date/Serial/Batch

Date

Data file name > Identified strings

16 characters or less

Data save > Save directory

Setup Item

Selectable Range or Selections

Default Value Setting

Directory name

20 characters or less

DATA0

Data save > Event data

Setup Item

Selectable Range or Selections

Default Value Setting

Sample rate

125ms/250ms/500ms/1s/2s/5s/10s/

1s

30s/1min/2min/5min/10min (depends on the model)

Mode

Free/Single/Repeat

Free

Data length

10min to 31day (depends on the sample rate)

1h

Pre-trigger

0/5/25/50/75/95/100

0

Trigger signal > Key

On/Off

On

Data save > Batch text

Setup Item

Selectable Range or Selections

Default Value Setting

Text field number

Numerical value (1 to 8)

1

Text field > Title of field

20 characters or less

Text field > Characters

30 characters or less