• Basic setting > Indicator

You can choose to make the alarm displays behave in the following ways.

Settings

Description

Nonhold

Clears the alarm indication when the alarm condition is released (returns to

normal condition).

Hold

Holds the alarm indication until an alarm acknowledge operation is performed.

• Internal Switch > AND

Select the internal switches that are to operate using AND logic. Set the range

of internal switches (from the first internal switch) to take the AND logic. All
subsequent switches will be set to OR logic.

• Relay > AND

Select the relays that are to operate using AND logic. Set the range of relays (from

the first alarm relay) to take the AND logic. All subsequent relays will be set to OR
logic. Available settings are

None, I01 (I01 only), I01-I02 (I01 and I02), I01-I03 (I01

to I03), etc. Only alarm output relays that are installed are valid.

Note

When reflash is turned ON, the operation of the first three output relays is fixed to OR logic.
Specifying

AND produces no effect.

• Relay > Action

Select whether the alarm output relay is energized or de-energized when an alarm

occurs. The setting applies to all alarm output relays.

• Relay > Hold

You can choose to make the alarm output relays behave in the following ways. This

setting applies to all relays.

Settings

Description

Nonhold

Turns the output relay OFF when the alarm condition is released (returns to

normal condition).

Hold

Holds the output relay at ON until an alarm acknowledge operation is performed.

Note

When reflash is turned ON, the operation of the first three output relays is set to nonhold.
Specifying

Hold produces no effect.

• Relay > Relay Action on Ack

You can select the relay output status that is enabled after the AlarmACK operation

from the following two settings.

Settings

Description

Normal

The relay is deactivated when the alarm ACK operation is executed. If the

condition for activating the alarm output relay is met in the next scan interval, the

relay is activated.

This operation is valid only when the alarm output relay is set to

Hold.

Reset

The relay is deactivated when the alarm ACK operation is executed. If a new

condition for activating the alarm output relay is met, the relay is activated.

3.5 Setting the Auxiliary Alarm Function