7-2

IM 04L21B01-01EN

Setup Items

• Logic box number

You can set up to 40.

• Event action > Event

The condition to execute the action.

Settings

Description

None

Not use.

Remote

Select the remote control input terminal number.

Relay

Select the alarm output relay number. During Edge operation, a change

from deactivated to activated is an event.

Switch

Select the internal switch number. During Edge operation, a change from off

to on is an event.

Timer

Select the timer number.

Matchtime

Select the match timer number.

Alarm

During Edge operation, a change from “no alarms are active” to “at least

one alarm is active” is an event.

USER key

-

• Event action > Action

The action to be executed when an event occurs.

Settings

Description

Memory

-

Start

-

Stop

-

Trigger

Can be specified when the FX is configured to record event data.

AlarmACK Cannot be specified when the event is set to

Relay, Switch, or Alarm.

Math

Can be specified on FXs with the /M1, /PM1, or /PWR1 option.

MathStrt

Start computation. Can be specified on FXs with the /M1, /PM1, or /PWR1 option.

MathStop

Stop computation. Can be specified on FXs with the /M1, /PM1, or /PWR1 option.

Math rst

Reset computation. Can be specified on FXs with the /M1, /PM1, or /PWR1 option.

SaveDisp

Can be specified when the FX is configured to record display data.

SaveEvt

Can be specified when the FX is configured to record event data.

Message

Set the message number to write the message and the destination. Set the

message destination to all groups (All) or a group number.

Snap

Snapshot

Rate1/2

Can be specified when the function for switching between the trend interval and

the secondary trend interval is enabled.

M.sample

Manual sampling

TimerRst

Cannot be specified when the event is set to

Timer.

Group

Specify the number of the group to be displayed.

Flag

Can be specified on FXs with the /M1, /PM1, or /PWR1 option.

Time adj

Can be specified only when the event is set to

Remote.

PnlLoad

Can be specified only when the event is set to

Remote.

7.1 Setting the Event Action Function

(Including the remote control function of the /R1 and /PM1 options and the USER key)