7-3
IM 04L21B01-01EN
Customizing
Actions Using the Event
Action and
Remote Control Functions (/R1 and /PM1 Options)
3
2
1
4
5
6
7
8
9
10
11
12
13
14
App
Index
• Timer
Timer used by event action. Used also in the TLOG computation of the computation
function.
* The timer cannot be changed while memory sampling or computation is in progress.
• Timer No.
Up to four timers (1 to 4) can be set.
When Using an Absolute Timer
• Mode
Select
Absolute.
• Interval
Select the interval from the available settings between 1min to 24h.
• Ref.time
Set the time in the range of hour 0 to hour 23.
When Using a Relative Timer
• Mode
Select
Relative.
• Interval
Set the interval in the range of 00:01 (1 min) to 24:00 (24 hours).
• Reset at Math Start
On: Resets the timer when computation is started. The resetting of the timer is not
considered to be a timeout. Even if the timer is used as an event, the action is not
executed.
• Match Time Timer
Set the time match condition used in event action.
* The condition cannot be changed while memory sampling or computation is in progress.
• Timer number
You can set up to four match time conditions (1 to 4).
• Kind
Setting
Description
Day
The condition is matched once a day.
Week
The condition is matched once a week.
Month
The condition is matched once a month.
Set the items with check marks in the following table depending on the Kind setting.
Setup Item
Kind
Day
Week
Month
Day
Day of the week
Hour:Minute
• Month
Specify the month.
• Day
Set the day.
• Day of the week
Set the day of the week.
• Hour:Minute
Set the time in the range of 00:00 to 23:59.
• Timer action
Settings
Description
Single
Executes the action once when the condition is met.
Repeat
Executes the action at every specified time.
7.1 Setting the Event Action Function