beautypg.com

App index, Events – Yokogawa Value Series FX1000 User Manual

Page 42

background image

1-33

IM 04L21B01-01EN

Overview of Functions

3

2

1

4

5

6

7

8

9

10

11

12

13

14

App

Index

1.6 Event Action and Remote Control Functions

(/R1 and /PM1 Options)

A specified action is carried out when an event occurs. This function is called event
action
. The remote control function (/R1 and /PM1 options) allows you to specify actions
to be performed when the terminal receives a contact input or an open collector signal.
The remote control function is configured using the event action function.
For the setting procedure, see section 7.1.

Events

• Events

Select from the following events.

Event

Level/Edge

1

Description

Remote

Level/Edge

ON/OFF of the remote control input.

Output relay

Level/Edge

Activated/Deactivated condition of the alarm output relay.

Internal switch

Level/Edge

The value, 0 (off) or 1 (on), of the internal switch.

Timer

Edge

Timer timeout.

Match time timer

Edge

When the time matches.

Alarm

Level/Edge

The state in which any alarm is occurring and the state in

which no alarm is occurring.

USER key

Edge

The operation of pressing the USER key.

1 For a description of level and edge, see “Miscellaneous” in this section.

• Output Relay, Internal Switch, Alarm

The output relay, internal switch, and alarm have two states, state A and state B,

which are explained in the table below.

Event

State A

State B

Output relay

Deactivated

Activated

Internal switch

OFF

ON

Alarm

No alarms

At least one alarm

When Edge Is Selected

An event occurs when state A changes to state B.

When Level Is Selected

There are action states that correspond to state A and state B.
See “Miscellaneous” and “Level and Edge” in this section.