3.1 Setting the Scan Interval and the Integration

Time of the A/D Converter

Select the scan interval and the integration time of the A/D converter.
For a description of the scan interval and the integration time of the A/D converter, see
section 1.1.

Setup Screen

Press

MENU (to switch to setting mode), hold down FUNC for 3 s (to switch to basic

setting mode), and select the

Menu tab > A/D, Memory.

Setup Items

• Scan interval > Scan mode

Fixed to

Normal.

• Scan interval > Scan interval

The selectable settings appear.

• Scan interval > A/D integrate

Select the A/D integration time as necessary. Only the selectable settings are

displayed.

Settings Description
Auto

The FX automatically detects the power supply frequency and sets the integration

time to 16.7 ms for 60 Hz and 20 ms for 50 Hz. Fixed to 20 ms on /P1 models

that use the 24 VDC power supply.

50Hz

Sets the integration time to 20 ms.

60Hz

Sets the integration time to 16.7 ms.

100ms

Sets the integration time to 100 ms (when the scan interval is 2 s or 5 s).

Chapter 3

Measurement Channels and Alarms