Global menu – Watlow EZ-ZONE PM Integrated Controller User Manual
Page 98
Watlow EZ-ZONE
®
PM Integrated Controller
•
95
•
Chapter 6 Setup Page
Setup Page
Dis-
play
Parameter Name
Description
Range
Default
Modbus Rela-
tive
Address
CIP
Class
Instance
Attribute
hex (dec)
Pro-
fibus
Index
Param-
eter ID
Data
Type
&
Read/
Write
[``Fn]
[ Fn]
Function Key (1 to 2)
Action Function
Program the EZ Key to
trigger an action.
Functions respond to a
level state change or an
edge level change.
Note:
The Limit Reset func-
tion is not available in
firmware revision 11.0
and above.
[none]
None (61)
[`r;en]
Remote Set Point en-
able (216)
[LMr]
Limit Reset, edge trig-
gered (82)
[usr;r]
User Set Restore, edge
triggered (227)
[P;LoC]
Keypad Lockout, level
triggered (217)
[ALM]
Alarm Reset, edge
triggered (6)
[`SiL]
Silence Alarms, edge
triggered (108)
[`AoF]
Control Loops Off and
Alarms to Non-alarm State,
level triggered (220)
[`F;AL]
Force Alarm to occur,
level triggered (218)
[idLE]
Idle Set Point, level
triggered (107)
[tUnE]
Tune, edge triggered
(98)
[MAn]
Manual, level trig-
gered (54)
[`oFF]
Switch Control Loop
Off, level triggered (90)
[`t;da]
TRU-TUNE+
®
Dis-
able, level triggered (219)
[P;diS]
Profile Disable, level
triggered (206)
[P;hoL]
Profile Hold/Resume,
level triggered (207)
[ProF]
Start Profile, edge
triggered (196)
[P;StS]
Profile Start/Stop,
level triggered (208)
[s;stp]
Start Step (1077)
None
Instance 1
Map 1 Map 2
1364
1604
Instance 2
Map 1 Map 2
1384 1624
0x6E (110)
3 to 4
3
138
10003 uint
RWES
[``Fi]
[ Fi]
Function Key (1 to 2)
Function Instance
Select which instance the
EZ Key will affect. If only
one instance is avail-
able, any selection will
affect it.
1 to 4
0
Instance 1
Map 1 Map 2
1366
1606
Instance 2
Map 1 Map 2
1386 1626
0x96 (110)
3 to 4
4
139
10004
- - - -
[gLbL]
[`Set]
Global Menu
[`C_F]
[ C_F]
Global
Display Units
Select which scale to use
for temperature.
[```F]
°F (30)
[```C]
°C (15)
°F
Instance 1
Map 1 Map 2
1838
2308
0x67 (103)
1
5
110
3005
uint
RWES
Note:
Some values will be rounded off to fit in the four-character display. Full values can be read
with other interfaces.
R: Read
W: Write
E:
EEPROM
S:
User
Set
Note:
When changing IP address the control power must be cycled for the new address to take effect.