beautypg.com

Global menu – Watlow EZ-ZONE PM Integrated Controller User Manual

Page 98

background image

Watlow EZ-ZONE

®

PM Integrated Controller

95

Chapter 6 Setup Page

Setup Page

Dis-

play

Parameter Name

Description

Range

Default

Modbus Rela-

tive

Address

CIP

Class

Instance

Attribute

hex (dec)

Pro-

fibus

Index

Param-

eter ID

Data

Type

&

Read/

Write

[``Fn]
[ Fn]

Function Key (1 to 2)
Action Function

Program the EZ Key to

trigger an action.

Functions respond to a

level state change or an

edge level change.

Note:

The Limit Reset func-

tion is not available in

firmware revision 11.0

and above.

[none]

None (61)

[`r;en]

Remote Set Point en-

able (216)

[LMr]

Limit Reset, edge trig-

gered (82)

[usr;r]

User Set Restore, edge

triggered (227)

[P;LoC]

Keypad Lockout, level

triggered (217)

[ALM]

Alarm Reset, edge

triggered (6)

[`SiL]

Silence Alarms, edge

triggered (108)

[`AoF]

Control Loops Off and

Alarms to Non-alarm State,

level triggered (220)

[`F;AL]

Force Alarm to occur,

level triggered (218)

[idLE]

Idle Set Point, level

triggered (107)

[tUnE]

Tune, edge triggered

(98)

[MAn]

Manual, level trig-

gered (54)

[`oFF]

Switch Control Loop

Off, level triggered (90)

[`t;da]

TRU-TUNE+

®

Dis-

able, level triggered (219)

[P;diS]

Profile Disable, level

triggered (206)

[P;hoL]

Profile Hold/Resume,

level triggered (207)

[ProF]

Start Profile, edge

triggered (196)

[P;StS]

Profile Start/Stop,

level triggered (208)

[s;stp]

Start Step (1077)

None

Instance 1

Map 1 Map 2

1364

1604

Instance 2

Map 1 Map 2

1384 1624

0x6E (110)

3 to 4

3

138

10003 uint

RWES

[``Fi]
[ Fi]

Function Key (1 to 2)
Function Instance

Select which instance the

EZ Key will affect. If only

one instance is avail-

able, any selection will

affect it.

1 to 4

0

Instance 1

Map 1 Map 2

1366

1606

Instance 2

Map 1 Map 2

1386 1626

0x96 (110)

3 to 4

4

139

10004

- - - -

[gLbL]
[`Set]
Global Menu

[`C_F]
[ C_F]

Global

Display Units

Select which scale to use

for temperature.

[```F]

°F (30)

[```C]

°C (15)

°F

Instance 1

Map 1 Map 2

1838

2308

0x67 (103)

1

5

110

3005

uint

RWES

Note:
Some values will be rounded off to fit in the four-character display. Full values can be read
with other interfaces.

R: Read

W: Write

E:

EEPROM

S:

User

Set

Note:

When changing IP address the control power must be cycled for the new address to take effect.