Watlow EZ-ZONE

®

PM Integrated Controller

37

Chapter 2 Install and Wire

Warning:

Óç

Use National Electric (NEC) or other

country-specific standard wiring and

safety practices when wiring and

connecting this controller to a power

source and to electrical sensors or

peripheral devices. Failure to do so

may result in damage to equipment

and property, and/or injury or loss
of life.

Note:

Maximum wire size termination and

torque rating:

• 0.0507 to 3.30 mm

2

(30 to 12

AWG) single-wire termination or

two 1.31 mm

2

(16 AWG)

• 0.8 Nm (7.0 lb.-in.) torque

Note:

Adjacent terminals may be labeled

differently, depending on the model

number.

Note:

To prevent damage to the control-

ler, do not connect wires to unused
terminals.

Note:

Maintain electrical isolation between

analog input 1, digital input-outputs,

switched dc/open collector outputs

and process outputs to prevent
ground loops.

Note:

The control output common termi-

nal and the digital common terminal

are referenced to different voltages

and must remain isolated.

Note:

This Equipment is suitable for use in

CLASS I, DIVISION 2, Groups A, B,

C and D or Non-Hazardous locations
only. Temperature Code T4A

Warning:

ç

Explosion Hazard - Dry contact clo-

sure Digital Inputs shall not be used

in Class I Division 2 Hazardous Loca-

tions unless switch used is approved
for this application.

Warning:

ç

Explosion Hazard – Substitution of

component may impair suitability

for CLASS I, DIVISION 2.

Warning:

ç

Explosion Hazard - Do not discon-

nect while the circuit is live or

unless the area is known to be free

of ignitable concentrations of flam-

mable substances.

Module Status (cont .)

Indicator State

Summary

Requirement

Steady Red

Major fault

If the device has detected a non-recoverable

major fault, the module status indicator shall

be steady red.

Flashing Green / Red Self-test

While the device is performing its power up

testing, the module status indicator shall be

flashing green / red.

Activity Status

Indicator State

Summary

Requirement

Flashing Green

Detects activity

If the MAC detects activity, the LED will be

flashing green.

Red

- - - -

If the MAC detects a collision, the LED will

be red.

Link Status

Indicator State

Summary

Requirement

Steady Off

Not powered,

unknown link speed

If the device cannot determine link speed

or power is off, the network status indicator

shall be steady off.

Green

- - - -

If cable is wired and connected correctly, the

LED will be Green.

DeviceNet™ Communications

CAN_L

V-

V+

CH

SH

CL

V-

T2

S2

R2

Slot B, E

V+

CAN_H

shield

Terminal

Signal

Function

V+

V+

DeviceNet™ power

CH

CAN_H

positive side of Devi-

ceNet™ bus

SH

shield

shield interconnect

CL

CAN_L

negative side of Devi-

ceNet™ bus

V-

V-

DeviceNet™ power

return

• Communications instance 2

Slot B (PM [6] _ _ _ _ _ - [5] _ _ _ _ _ _ )
Slot E (PM [4,8,9] _ _ _ _ _ - [5] _ _ _ _ _ _ )