beautypg.com

Watlow EZ-ZONE PM Integrated Controller User Manual

Page 100

background image

Watlow EZ-ZONE

®

PM Integrated Controller

97

Chapter 6 Setup Page

Setup Page

Dis-

play

Parameter Name

Description

Range

Default

Modbus Rela-

tive

Address

CIP

Class

Instance

Attribute

hex (dec)

Pro-

fibus

Index

Param-

eter ID

Data

Type

&

Read/

Write

[poti]
[Poti]

Global

Power Off Time

If profile is running and

power is lost, profile

will resume where it

left off provided time

set has not expired pri-

or to power restoration.

0 to 9999 seconds

0

Instance 1

Map 1 Map 2

- - - -

4484

7A (122)

1

0x49 (73)

- - - -

22073 uint

RWE

[sutb]
[Sutb]

Global

Synchronized Variable

Time Base

Used to acquire tighter

accuracy when running

a profile. A setting of

+0.01 would equate to

approximately +9 sec-

onds/day (faster) where

a setting of -0.01 would

equate to approximately

-9 seconds/day (slower).

-2.00 to 2.00 Percent

0.00

- - - -

- - - -

- - - -

- - - - float

RWE

[C;led]
[C.LEd]

Global

Communications LED

Action

Turns comms LED on or

off for selected comms

ports.

[Con1]

Comm port 1 (1189)

[Con2]

Comm port 2 (1190)

[both]

Comm port 1 and 2

(13)

[`off]

Off (62)

both

Instance 1

Map 1 Map 2

1856

2326

0x6A (103)

1

0x0E (14)

- - - -

3014

uint

RWES

[2one]
[Zone]

Global

Zone

Turns Zone LED on or

off based on selection.

[`off]

Off (62)

[``on]

On (63)

On

Instance 1

Map 1 Map 2

- - - -

2350

0x6A (103)

1

0x1A (26)

- - - -

3026

uint

RWES

[Chan]
[Chan]

Global

Channel

Turns Channel LED on

or off based on selection.

[`off]

Off (62)

[``on]

On (63)

On

Instance 1

Map 1 Map 2

- - - -

2352

0x6A (103)

1

0x1B (27)

- - - -

3027

uint

RWES

[d;prs]
[dPrS]

Global

Display Pairs

Defines the number of

Display Pairs.

1 to 10

2

Instance 1

Map 1 Map 2

- - - -

2354

0x6A (103)

1

0x1C (28)

- - - -

3028

uint

RWES

[`d;ti]
[ d.ti]

Global

Display Time

Time delay in toggling

between Display Pairs.

0 to 60

0

Instance 1

Map 1 Map 2

- - - -

2356

0x6A (103)

1

0x1D (29)

- - - -

3029

uint

RWES

[USr;S]
[USr.S]

Global

User Settings Save

Save all of this control-

ler's settings to the

selected set.

[SEt1]

User Set 1 (101)

[SEt2]

User Set 2 (102)

[none]

None (61)

None

Instance 1

Map 1 Map 2

26

26

0x(101)

1

0xE (14)

118

1014

uint

RWE

[USr;r]
[USr.r]

Global

User Settings Restore

Replace all of this con-

troller's settings with

another set.

[FCty]

Factory (31)

[none]

None (61)

[SEt1]

User Set 1 (101)

[SEt2]

User Set 2 (102)

None

Instance 1

Map 1 Map 2

24

24

0x65

(101)

1

0xD (13)

117

1013

uint

RWE

Note:
Some values will be rounded off to fit in the four-character display. Full values can be read
with other interfaces.

R: Read

W: Write

E:

EEPROM

S:

User

Set