Digital input / output menu – Watlow EZ-ZONE PM Integrated Controller User Manual

Page 78

background image

Watlow EZ-ZONE

®

PM Integrated Controller

75

Chapter 6 Setup Page

Setup Page

Dis-

play

Parameter Name

Description

Range

Default

Modbus Rela-

tive

Address

CIP

Class

Instance

Attribute

hex (dec)

Pro-

fibus

Index

Param-

eter ID

Data

Type

&

Read/

Write

[`dio]
[`Set]
Digital Input / Output Menu

[`dir]
[ dir]

Digital Input/Output (5

to 12)

Digital I/O Direction

Set this function to oper-

ate as an input or output.

Note:

Modbus Map 1 has in-

stances 5 through 8 only

[OtPt]

Output (68)

[iCon]

Input Dry Contact

(44)

[``in]

Input Voltage (193)

Output

Instance 5

Map 1 Map 2

1000

1120

Offset to next

instance

(Map 1 & Map

2) equals +30

0x6A (106)

5 to C (12)

1

82

6001

uint

RWES

[``Fn]
[ Fn]

Digital Output (5 to 12)

Output Function

Select what function will

drive this output.

Note:

Modbus Map 1 has in-

stances 5 through 8 only

[`oFF]

Off (62)

[Ent;b]

Profile Event Out B

(234)

[Ent;A]

Profile Event Out A

(233)

[SoF;2]

Special Function Out-

put 2 (1533)

[SoF;1]

Specia l Function Out-

put 1 (1532)

[CooL]

Cool (20)

[heat]

Heat (36)

[ALM]

Alarm (6)

Off

Instance 5

Map 1 Map 2

1008

1128

Offset to next

instance (Map

1 & Map 2)

equals +30

0x6A (106)

5 to C (12)

5

83

6005

uint

RWES

[``Fi]
[ Fi]

Digital Output (5 to 12)

Output Function In-

stance

Set the instance of the

function selected above.

Note:

Modbus Map 1 has in-

stances 5 through 8 only

1 to 4

1

Instance 5

Map 1 Map 2

1010

1130

Offset to next

instance (Map

1 & Map 2)

equals +30

0x6A (106)

5 to C (12)

6

84

6006

uint

RWES

[`o;Ct]
[ o.Ct]

Digital Output (5 to 12)

Output Control

Set the output control

type. This parameter

is only used with PID

control, but can be set

anytime.

Note:

Modbus Map 1 has in-

stances 5 through 8 only

[`Ftb]

Fixed Time Base (34)

[`utb]

Variable Time Base

(103)

Fixed

Time

Base

Instance 5

Map 1 Map 2

1002

1122

Offset to next

instance (Map

1 & Map 2)

equals +30

0x6A (106)

5 to C (12)

2

85

6002

uint

RWES

[`o;tb]
[ o.tb]

Digital Output (5 to 12)

Output Time Base

Set the time base for

fixed-time-base control.

Note:

Modbus Map 1 has in-

stances 5 through 8 only

[ 0.1 for Fast and Bi-Direc-

tional outputs, 5.0 for Slow

outputs] to 60

5.0

Instance 5

Map 1 Map 2

1004

1124

Offset to next

instance (Map

1 & Map 2)

equals +30

0x6A (106)

5 to C (12)

3

86

6003

float

RWES

Note:
Some values will be rounded off to fit in the four-character display. Full values can be read
with other interfaces.

R: Read

W: Write

E:

EEPROM

S:

User

Set