Watlow EZ-ZONE

®

PM Integrated Controller

94

Chapter 6 Setup Page

Setup Page

Dis-

play

Parameter Name

Description

Range

Default

Modbus Rela-

tive

Address

CIP

Class

Instance

Attribute

hex (dec)

Pro-

fibus

Index

Param-

eter ID

Data

Type

&

Read/

Write

[`oF;t]
[ oF.t]

Special Output (1)

Off Time

At a minimum stay off

specified amount of time.

0 to 9,999 seconds

20

Instance 1

Map 1 Map 2

- - - -

3884

0x87 (135)

1

0x17 (23)

191

35023 uint

RWES

[``t;t]
[ t.t]

Special Output (1)

Valve Travel Time

The amount of time it

takes the valve to fully

open and then fully close.

10 to 9,999 seconds

120

Instance 1

Map 1 Map 2

- - - -

3886

0x87 (135)

1

0x18 (24)

192

35024 uint

RWES

[``db]
[ db]

Special Output (1)

Dead Band

Output power needs to

change by specified level

prior to turning on.

1.0 to 100.0%

2

Instance 1

Map 1 Map 2

- - - -

3888

0x87 (135)

1

0x19 (25)

193

35025 float

RWES

[`t;dL]
[ t.dL]

Special Output (1)

Time Delay

If requested power is

0.0% for longer than the

specified Time Delay, the

compressor will shut off.

0 to 9,999 seconds

0

Instance 1

Map 1 Map 2

- - - -

3890

0x87 (135)

1

0x1A (26)

- - - -

35026 uint

RWES

[`FUn]
[`Set]
Function Key

`leu]
[ LEv]

Function Key (3 to 4)

Active Level

The Function Key will

always power up in the

low state.

Pressing the Function

Key will toggle the se-

lected action.

high]

High (37)

[Low]

Low (53)

High

Instance 3

Map 1 Map 2

1360

1600

Instance 4

Map 1 Map 2

1380 1620

0x6E (110)

3 to 4

1

137

10001 uint

RWES

Note:
Some values will be rounded off to fit in the four-character display. Full values can be read
with other interfaces.

R: Read

W: Write

E:

EEPROM

S:

User

Set