Chapter 5 Operations Page

Operations Page

Dis-

play

Parameter name

Description

Range

Default

Modbus

Relative Ad-

dress

CIP

Class

Instance

Attribute

hex (dec)

Profibus

Index

Param-

eter ID

Data

Type

& Read/

Write

[``Ai]
[oPEr]
Analog Input Menu

[`Ain]
[ Ain]

Analog Input (1 to 2)

Analog Input Value

View the process value.

Note:

Ensure that the Input

Error (below) indicates

no error (61) when

reading this value us-

ing a field bus protocol.

If an error exists, the

last known value prior

to the error occurring

will be returned.

-1,999.000 to 9,999.000°F

or units

-1,128.000 to 5,537.000°C

Instance 1

Map 1 Map 2

360 360

Instance 2

Map 1 Map 2

440 450

0x68 (104)

1 to 2

1

0

4001

float

R

[`i;Er]
[ i.Er]

Analog Input (1 to 2)

Input Error

View the cause of the

most recent error. If

the [Attn] message is
[Er;i1]

or [Er;i2], this

parameter will display

the cause of the input

error.

[nonE]

None (61)

[OPEn]

Open (65)

[FAiL]

Fail (32)

[Shrt]

Shorted (127)

[`E;M]

Measurement Er-

ror (140)

[E;CAL]

Bad Calibration

Data (139)

[Er;Ab]

Ambient Error (9)

[E;;Rtd]

RTD Error (141)

[Nsrc]

Not Sourced (246)

None

Instance 1

Map 1 Map 2

362 362

Instance 2

Map 1 Map 2

442 452

0x68 (104)

1 to 2

2

1

4002

uint

R

[`i;Ca]
[ i.CA]

Analog Input (1 to 2)

Calibration Offset

Offset the input reading

to compensate for lead

wire resistance or other

factors that cause the in-

put reading to vary from

the actual process value.

-1,999.000 to 9,999.000°F

or units

-1,110.555 to 5,555.000°C

0.0

Instance 1

Map 1 Map 2

382 382

Instance 2

Map 1 Map 2

462 472

0x68 (104)

1 to 2

0xC (12)

2

4012

float

RWES

[`Lnr]
[oPEr]
Linearization Menu

[`Su;A]
[ Su.A]

Linearization (1 to 2)

Source Value A

View the value of Source

A.

Source A of Lineariza-

tion 1 is connected to

Analog Input 1

Source A of Lineariza-

tion 2 is connected to

Analog Input 2

-1,999.000 to 9,999.000°F

or units

-1,128.000 to 5,537.000°C

Instance 1

Map 1 Map 2

- - - - 3566

Instance 2

Map 1 Map 2

- - - - 3636

0x86 (134)

1 to 2

4

- - - -

34004

float

R

[oFSt]
[oFSt]

Linearization (1 to 2)

Offset

Set an offset to be ap-

plied to this function's

output.

-1,999.000 to 9,999.000°F

or units

-1,128.000 to 5,537.000°C

0

Instance 1

Map 1 Map 2

- - - -

3570

Instance 2

Map 1 Map 2

- - - -

3640

0x86 (134)

1 to 2

6

- - - -

34006

float

RWES

Note:
Some values will be rounded off to fit in the four-character display. Full values can
be read with other interfaces.

R: Read

W: Write

E: EEPROM

S: User