Watlow EZ-ZONE
®
PM Integrated Controller
•
89
•
Chapter 6 Setup Page
Setup Page
Dis-
play
Parameter Name
Description
Range
Default
Modbus Rela-
tive
Address
CIP
Class
Instance
Attribute
hex (dec)
Pro-
fibus
Index
Param-
eter ID
Data
Type
&
Read/
Write
[loop]
[LooP]
Alarm (1 to 4)
Control Loop
Set the instance of the
Set Point Closed, Control
Loop, that will be refer-
enced by the deviation
alarm.
Note:
Not available on single
loop models.
1 to 2
1
Instance 1
Map 1 Map 2
1524
1924
Offset to next
instance (Map
1 +50, Map 2
+60)
0x6D (109)
1 to 2
0x17 (23)
23
9023
uint
RWES
[`A;hy]
[ A.hy]
Alarm (1 to 4)
Alarm Hysteresis
Set the hysteresis for an
alarm. This determines
how far into the safe
region the process value
needs to move before the
alarm can be cleared.
0.001 to 9,999.000°F or units
0.001 to 5,555.000°C
1.0°F or
units
1.0°C
Instance 1
Map 1 Map 2
1484
1884
Offset to next
instance (Map
1 equals +50,
Map 2 +60)
0x6D (109)
1 to 4
3
24
9003
float
RWES
[`A;Lg]
[ A.Lg]
Alarm (1 to 4)
Alarm Logic
Select what the output
condition will be during
the alarm state.
[`AL;C]
Close On Alarm (17)
[`AL;o]
Open On Alarm (66)
Close On
Alarm
Instance 1
Map 1 Map 2
1488
1888
Offset to next
instance (Map
1 +50, Map 2
+60)
0x6D (109)
1 to 4
5
25
9005
uint
RWES
[`A;Sd]
[ A.Sd]
Alarm (1 to 4)
Alarm Sides
Select which side or sides
will trigger this alarm.
[both]
Both (13)
[high]
High (37)
[LoW]
Low (53)
Both
Instance 1
Map 1 Map 2
1486
1886
Offset to next
instance (Map
1 +50, Map 2
+60)
0x6D (109)
1 to 4
4
26
9004
uint
RWES
[`A;Lo]
[ A.Lo]
Alarm (1 to 4)
Alarm Low Set Point
If Alarm Type (Setup
Page, Alarm Menu) is
set to:
process - set the process
value that will trigger
a low alarm.
deviation - set the span
of units from the closed
loop set point that will
trigger a low alarm. A
negative set point rep-
resents a value below
closed loop set point. A
positive set point rep-
resents a value above
closed loop set point.
-1,999.000 to 9,999.000°F or
units
-1,128.000 to 5,537.000°C
32.0°F
or units
0.0°C
Instance 1
Map 1 Map 2
1482 1882
Offset to next
instance (Map
1 +50, Map 2
+60)
0x6D
(109)
1 to 4
2
18
9002
float
RWES
Note:
Some values will be rounded off to fit in the four-character display. Full values can be read
with other interfaces.
R: Read
W: Write
E:
EEPROM
S:
User
Set