Chapter 6 Setup Page

Setup Page

Dis-

play

Parameter Name

Description

Range

Default

Modbus Rela-

tive

Address

CIP

Class

Instance

Attribute

hex (dec)

Pro-

fibus

Index

Param-

eter ID

Data

Type

&

Read/

Write

[`l;st]
[ L.St]

Limit (1)

Limit Status **

Reflects whether or not

the limit is in a safe or

failed mode.

[fail]

Fail (32)

[safe]

Safe (1667)

- - - -

Instance 1

Map 1 Map 2

- - - -

744

0x70 (112)

1

0x0D (13)

- - - -

12013 uint

R

[`L;it]
[ L.it]

Limit

Integrate with System

In a limit state the con-

troller will turn off the

outputs, terminate an

active profile and freeze

PID and TRU-TUNE+

®

calculations.

[``no]

No (59)

[`YES]

Yes (106)

No

Instance 1

Map 1 Map 2

694

734

0x70 (112)

1

8

- - - -

12008 uint

RWES

No

Dis-

play

Limit (1)

Limit State

Clear limit once limit

condition is cleared.

[`off]

Off (62)

[none]

None (61)

[`li;h]

Limit High (51)

[`li;l]

Limit Low (52)

[`err]

Error (28)

- - - -

Instance 1

Map 1 Map 2

690

730

0x70 (112)

1

6

- - - -

12006 uint

R

[LooP]
[`Set]
Control Loop Menu

[`h;Ag]
[ h.Ag]

Control Loop (1 to 2)

Heat Algorithm

Set the heat control

method.

[`oFF]

Off (62)

[`Pid]

PID (71)

[on;of]

On-Off (64)

PID

Instance 1

Map 1 Map 2

1884

2364

Instance 2

Map 1 Map 2

1954 2434

0x97 (151)

1 to 2

3

72

8003

uint

RWES

[`C;Ag]
[ C.Ag]

Control Loop (1 to 2)

Cool Algorithm

Set the cool control

method.

[`oFF]

Off (62)

[`Pid]

PID (71)

[on;of]

On-Off (64)

Off

Instance 1

Map 1 Map 2

1886

2366

Instance 2

Map 1 Map 2

1956 2436

0x97 (151)

1 to 2

4

73

8004

uint

RWES

[`C;Cr]
[ C.Cr]

Control Loop (1 to 2)

Cool Output Curve

Select a cool output

curve to change the

responsiveness of the

system.

[`oFF]

Off (62)

[`Cr;A]

Non-linear Curve 1

(214)

[`Cr;b]

Non-linear Curve 2

(215)

Off

Instance 1

Map 1 Map 2

1888

2368

Instance 2

Map 1 Map 2

1958

2438

0x97 (151)

1 to 2

5

- - - -

8038

uint

RWES

[`h;Pb]
[ h.Pb]

Control Loop (1 to 2)

Heat Proportional

Band

Set the PID proportional

band for the heat out-

puts.

0.001 to 9,999.000°F or units

-1,110.555 to 5,555.000°C

25.0°F or

units

14.0°C

Instance 1

Map 1 Map 2

1890 2370

Instance 2

Map 1 Map 2

1960

2440

0x97

(151)

1 to 2

6

65

8009

float

RWES

[`h;hy]
[ h.hy]

Control Loop (1 to 2)

Heat Hysteresis

Set the control switch-

ing hysteresis for on-off

control. This determines

how far into the “on”

region the process value

needs to move before

the output turns on.

0.001 to 9,999.000°F or units

0.001 to 5,555.000°C

3.0°F or

units

2.0°C

Instance 1

Map 1 Map 2

1900 2380

Instance 2

Map 1 Map 2

1970

2450

0x97

(151)

1 to 2

0xB (11)

66

8010

float

RWES

Note:
Some values will be rounded off to fit in the four-character display. Full values can be read
with other interfaces.

R: Read

W: Write

E:

EEPROM

S:

User

Set