Watlow EZ-ZONE PM Integrated Controller User Manual
Page 80
Watlow EZ-ZONE
®
PM Integrated Controller
•
77
•
Chapter 6 Setup Page
Setup Page
Dis-
play
Parameter Name
Description
Range
Default
Modbus Rela-
tive
Address
CIP
Class
Instance
Attribute
hex (dec)
Pro-
fibus
Index
Param-
eter ID
Data
Type
&
Read/
Write
[``Fn]
[ Fn]
Digital Input (5 to 6)
Action Function
Select the function that
will be triggered by a
true state for Digital In-
puts 5 to 6.
[none]
None (61)
[s;stp]
Start Step (1077)
[P;StS]
Profile Start/Stop,
level triggered (208)
[ProF]
Start Profile, edge
triggered (196)
[P;hoL]
Profile Hold/Resume,
level triggered (207)
[P;diS]
Profile Disable, level
triggered (206)
[`t;da]
TRU-TUNE+
®
Dis-
able, level triggered (219)
[`oFF]
Switch Control Loop
Off, level triggered (90)
[MAn]
Manual, level trig-
gered (54)
[tUnE]
Tune, edge triggered
(98)
[idLE]
Idle Set Point, level
triggered (107)
[`F;AL]
Force Alarm to occur,
level triggered (218)
[`AoF]
Control Loops Off and
Alarms to Non-alarm State,
level triggered (220)
[`SiL]
Silence Alarms, edge
triggered (108)
[ALM]
Alarm Reset, edge
triggered (6)
[P;LoC]
Keypad Lockout, level
triggered (217)
[usr;r]
User Set Restore, edge
triggered (227)
[LMr]
Limit Reset, edge trig-
gered (82)
[`r;en]
Remote Set Point en-
able (216)
None
Instance 5
Map 1 Map 2
1324
1564
Offset to next
instance (Map
1 & Map 2)
equals +20
0x6E (110)
5 to 6
3
138
10003 uint
RWES
Note:
Some values will be rounded off to fit in the four-character display. Full values can be read
with other interfaces.
R: Read
W: Write
E:
EEPROM
S:
User
Set