Page 80

background image

Watlow EZ-ZONE

®

PM Integrated Controller

77

Chapter 6 Setup Page

Setup Page

Dis-

play

Parameter Name

Description

Range

Default

Modbus Rela-

tive

Address

CIP

Class

Instance

Attribute

hex (dec)

Pro-

fibus

Index

Param-

eter ID

Data

Type

&

Read/

Write

[``Fn]
[ Fn]

Digital Input (5 to 6)

Action Function

Select the function that

will be triggered by a

true state for Digital In-

puts 5 to 6.

[none]

None (61)

[s;stp]

Start Step (1077)

[P;StS]

Profile Start/Stop,

level triggered (208)

[ProF]

Start Profile, edge

triggered (196)

[P;hoL]

Profile Hold/Resume,

level triggered (207)

[P;diS]

Profile Disable, level

triggered (206)

[`t;da]

TRU-TUNE+

®

Dis-

able, level triggered (219)

[`oFF]

Switch Control Loop

Off, level triggered (90)

[MAn]

Manual, level trig-

gered (54)

[tUnE]

Tune, edge triggered

(98)

[idLE]

Idle Set Point, level

triggered (107)

[`F;AL]

Force Alarm to occur,

level triggered (218)

[`AoF]

Control Loops Off and

Alarms to Non-alarm State,

level triggered (220)

[`SiL]

Silence Alarms, edge

triggered (108)

[ALM]

Alarm Reset, edge

triggered (6)

[P;LoC]

Keypad Lockout, level

triggered (217)

[usr;r]

User Set Restore, edge

triggered (227)

[LMr]

Limit Reset, edge trig-

gered (82)

[`r;en]

Remote Set Point en-

able (216)

None

Instance 5

Map 1 Map 2

1324

1564

Offset to next

instance (Map

1 & Map 2)

equals +20

0x6E (110)

5 to 6

3

138

10003 uint

RWES

Note:
Some values will be rounded off to fit in the four-character display. Full values can be read
with other interfaces.

R: Read

W: Write

E:

EEPROM

S:

User

Set