Calibration menu, Watlow ez-zone, Pm integrated controller – Watlow EZ-ZONE PM Integrated Controller User Manual

Page 121: Chapter 8 factory page

background image

Watlow EZ-ZONE

®

PM Integrated Controller

118

Chapter 8 Factory Page

Factory Page

Dis-

play

Parameter Name

Description

Range

Default

Modbus

Relative Ad-

dress

CIP

Class

Instance

Attribute

hex (dec)

Pro-

fibus

Index

Param-

eter ID

Data

Type

&

Read/

Write

[iP;A6]
[ip.F6]

Diagnostics

IP Actual Address Part

6

Actual IP address of this

module.

Note:

Although it appears as if

this can be changed here

this is a read only param-

eter. Go to Setup Page and

then the Com Menu to

change.

0 to 255

1

- - - -

- - - -

- - - -

17019 R

[`CAL]
[FCty]
Calibration Menu

[`Mu]
[ Mv]

Calibration (1 to 2)

Electrical Measure-

ment

Read the raw electrical

value for this input in

the units corresponding

to the Sensor Type (Set-

up Page, Analog Input

Menu) setting.

-3.4e38 to 3.4e38

Instance 1

Map 1

Map 2

400

400

Instance 2

Map 1

Map 2

480

490

0x68

(104)

1 to 2

0x15 (21)

- - - -

4021

float

R

[ELi;o]
[ELi.o]

Calibration (1 to 2)

Electrical Input Offset

Change this value to

calibrate the low end of

the input range.

-1,999.000 to 9,999.000

0.0

Instance 1

Map 1

Map 2

378

378

Instance 2

Map 1

Map 2

458

468

0x68

(104)

1 to 2

0x0A (10)

- - - -

4010

float

RWES

[ELi;S]
[ELi.S]

Calibration (1 to 2)

Electrical Input Slope

Adjust this value to

calibrate the slope of the

input value.

-1,999.000 to 9,999.000

1.0

Instance 1

Map 1

Map 2

380

380

Instance 2

Map 1

Map 2

460

470

0x68

(104)

1 to 2

0xB (11)

- - - -

4011

float

RWES

[ELo;o]
[ELo.o]

Calibration (1 or 3)

Electrical Output

Offset

Change this value to

calibrate the low end of

the output range.

-1,999.000 to 9,999.000

0.0

Instance 1

Map 1

Map 2

728

848

Instance 3

Map 1

Map 2

808

928

0x76

(118)

1 or 3

5

- - - -

18005

float

RWES

[ELo;S]
[ELo.S]

Calibration (1 or 3)

Electrical Output

Slope

Adjust this value to

calibrate the slope of the

output value.

-1,999.000 to 9,999.000

1.0

Instance 1

Map 1

Map 2

730

850

Instance 3

Map 1

Map 2

810

930

0x76

(118)

1 or 3

6

- - - -

18006

float

RWES

[``Pn]
[ Pn]

Calibration (1 to 3)

Part Number

Displays current set-

ting for control model

number.

[fCty]

Factory

[User]

User

Factory

- - - -

- - - -

- - - -

- - - -

uint

R

[Code]
[CodE]

Calibration (1 to 3)

Public Key

Changes the control to a

PM Express or back to

original model number

as shown on the side of

the control.

[2501]

PM Express

[`606]

Factory model num-

ber

4999

- - - -

- - - -

- - - -

- - - -

uint

RWES

Note:

Some values will be rounded off to fit in the four-character display. Full values can be read
with other interfaces.

If there is only one instance of a menu, no submenus will appear.

R: Read

W: Write

E:

EEPROM

S:

User

Set