Calibration menu, Watlow ez-zone, Pm integrated controller – Watlow EZ-ZONE PM Integrated Controller User Manual
Page 121: Chapter 8 factory page
Watlow EZ-ZONE
®
PM Integrated Controller
•
118
•
Chapter 8 Factory Page
Factory Page
Dis-
play
Parameter Name
Description
Range
Default
Modbus
Relative Ad-
dress
CIP
Class
Instance
Attribute
hex (dec)
Pro-
fibus
Index
Param-
eter ID
Data
Type
&
Read/
Write
[iP;A6]
[ip.F6]
Diagnostics
IP Actual Address Part
6
Actual IP address of this
module.
Note:
Although it appears as if
this can be changed here
this is a read only param-
eter. Go to Setup Page and
then the Com Menu to
change.
0 to 255
1
- - - -
- - - -
- - - -
17019 R
[`CAL]
[FCty]
Calibration Menu
[`Mu]
[ Mv]
Calibration (1 to 2)
Electrical Measure-
ment
Read the raw electrical
value for this input in
the units corresponding
to the Sensor Type (Set-
up Page, Analog Input
Menu) setting.
-3.4e38 to 3.4e38
Instance 1
Map 1
Map 2
400
400
Instance 2
Map 1
Map 2
480
490
0x68
(104)
1 to 2
0x15 (21)
- - - -
4021
float
R
[ELi;o]
[ELi.o]
Calibration (1 to 2)
Electrical Input Offset
Change this value to
calibrate the low end of
the input range.
-1,999.000 to 9,999.000
0.0
Instance 1
Map 1
Map 2
378
378
Instance 2
Map 1
Map 2
458
468
0x68
(104)
1 to 2
0x0A (10)
- - - -
4010
float
RWES
[ELi;S]
[ELi.S]
Calibration (1 to 2)
Electrical Input Slope
Adjust this value to
calibrate the slope of the
input value.
-1,999.000 to 9,999.000
1.0
Instance 1
Map 1
Map 2
380
380
Instance 2
Map 1
Map 2
460
470
0x68
(104)
1 to 2
0xB (11)
- - - -
4011
float
RWES
[ELo;o]
[ELo.o]
Calibration (1 or 3)
Electrical Output
Offset
Change this value to
calibrate the low end of
the output range.
-1,999.000 to 9,999.000
0.0
Instance 1
Map 1
Map 2
728
848
Instance 3
Map 1
Map 2
808
928
0x76
(118)
1 or 3
5
- - - -
18005
float
RWES
[ELo;S]
[ELo.S]
Calibration (1 or 3)
Electrical Output
Slope
Adjust this value to
calibrate the slope of the
output value.
-1,999.000 to 9,999.000
1.0
Instance 1
Map 1
Map 2
730
850
Instance 3
Map 1
Map 2
810
930
0x76
(118)
1 or 3
6
- - - -
18006
float
RWES
[``Pn]
[ Pn]
Calibration (1 to 3)
Part Number
Displays current set-
ting for control model
number.
[fCty]
Factory
[User]
User
Factory
- - - -
- - - -
- - - -
- - - -
uint
R
[Code]
[CodE]
Calibration (1 to 3)
Public Key
Changes the control to a
PM Express or back to
original model number
as shown on the side of
the control.
[2501]
PM Express
[`606]
Factory model num-
ber
4999
- - - -
- - - -
- - - -
- - - -
uint
RWES
Note:
Some values will be rounded off to fit in the four-character display. Full values can be read
with other interfaces.
If there is only one instance of a menu, no submenus will appear.
R: Read
W: Write
E:
EEPROM
S:
User
Set