Analog input menu – Watlow EZ-ZONE PM Integrated Controller User Manual
Page 72
Watlow EZ-ZONE
®
PM Integrated Controller
•
69
•
Chapter 6 Setup Page
Setup Page
Dis-
play
Parameter Name
Description
Range
Default
Modbus Rela-
tive
Address
CIP
Class
Instance
Attribute
hex (dec)
Pro-
fibus
Index
Param-
eter ID
Data
Type
&
Read/
Write
[``Ai]
[`Set]
Analog Input Menu
[`Sen]
[ SEn]
Analog Input (1 to 2)
Sensor Type
Set the analog sensor
type to match the device
wired to this input.
Note:
There is no open-sensor
detection for process inputs.
[`oFF]
Off (62)
[``tC]
Thermocouple (95)
[`mu]
Millivolts (56)
[uolT]
Volts dc (104)
[`MA]
Milliamps dc (112)
[r0;1H]
RTD 100 Ω (113)
[r1;0H]
RTD 1,000 Ω (114)
[`Pot]
Potentiometer 1 kΩ
(155)
[thEr]
Thermistor (229)
Off
Instance 1
Map 1 Map 2
368 368
Instance 2
Map 1 Map 2
448
458
0x68 (104)
1 to 2
5
3
4005
uint
RWES
[`Lin]
[ Lin]
Analog Input (1 to 2)
TC Linearization
Set the linearization to
match the thermocouple
wired to this input.
[```b]
B (11)
[```H]
K (48)
[```C]
C (15)
[```n]
N (58)
[```d]
D (23)
[```r]
R (80)
[```E]
E (26)
[```S]
S (84)
[```F]
F (30)
[```t]
T (93)
[```J]
J (46)
J
Instance 1
Map 1 Map 2
370 370
Instance 2
Map 1 Map 2
450
460
0x68 (104)
1 to 2
6
4
4006
uint
RWES
[`Rt;L]
[ rt.L]
Analog Input (1 to 2)
RTD Leads
Set to match the num-
ber of leads on the RTD
wired to this input.
[```2]
2 (1)
[```3]
3 (2)
2
Instance 1
Map 1 Map 2
372 372
Instance 2
Map 1 Map 2
452
462
0x68 (104)
1 to 2
7
- - - -
4007
uint
RWES
[Unit]
[Unit]
Analog Input (1 to 2)
Units
Set the type of units the
sensor will measure.
[`A;tP]
Absolute Temperature
(1540)
[``rh]
Relative Humidity
(1538)
[`Pro]
Process (75)
[PWr]
Power (73)
Process
Instance 1
Map 1 Map 2
- - - -
442
Instance 2
Map 1 Map 2
- - - -
532
0x68 (104)
1 to 2
0x2A (42)
5
4042
uint
RWES
[`S;Lo]
[ S.Lo]
Analog Input (1 to 2)
Scale Low
Set the low scale for pro-
cess inputs. This value,
in millivolts, volts or mil-
liamps, will correspond to
the Range Low output of
this function block.
-100.0 to 1,000.0
0.0
Instance 1
Map 1 Map 2
388
388
Instance 2
Map 1 Map 2
468
478
0x68 (104)
1 to 2
0xF (15)
6
4015
float
RWES
[`S;hi]
[ S.hi]
Analog Input (1 to 2)
Scale High
Set the high scale for
process inputs. This
value, in millivolts, volts
or milliamps, will corre-
spond to the Range High
output of this function
block.
-100.0 to 1,000.0
20.0
Instance 1
Map 1 Map 2
390
390
Instance 2
Map 1 Map 2
470
480
0x68 (104)
1 to 2
0x10 (16)
7
4016
float
RWES
[`r;Lo]
[ r.Lo]
Analog Input (1 to 2)
Range Low
Set the low range for this
function block's output.
-1,999.000 to 9,999.000
0.0
Instance 1
Map 1 Map 2
392
392
Instance 2
Map 1 Map 2
472
482
0x68 (104)
1 to 2
0x11 (17)
8
4017
float
RWES
Note:
Some values will be rounded off to fit in the four-character display. Full values can be read
with other interfaces.
R: Read
W: Write
E:
EEPROM
S:
User
Set