Chapter 6 Setup Page

Setup Page

Dis-

play

Parameter Name

Description

Range

Default

Modbus Rela-

tive

Address

CIP

Class

Instance

Attribute

hex (dec)

Pro-

fibus

Index

Param-

eter ID

Data

Type

&

Read/

Write

[``Ai]
[`Set]
Analog Input Menu

[`Sen]
[ SEn]

Analog Input (1 to 2)

Sensor Type

Set the analog sensor

type to match the device

wired to this input.

Note:
There is no open-sensor
detection for process inputs.

[`oFF]

Off (62)

[``tC]

Thermocouple (95)

[`mu]

Millivolts (56)

[uolT]

Volts dc (104)

[`MA]

Milliamps dc (112)

[r0;1H]

RTD 100 Ω (113)

[r1;0H]

RTD 1,000 Ω (114)

[`Pot]

Potentiometer 1 kΩ

(155)

[thEr]

Thermistor (229)

Off

Instance 1

Map 1 Map 2

368 368

Instance 2

Map 1 Map 2

448

458

0x68 (104)

1 to 2

5

3

4005

uint

RWES

[`Lin]
[ Lin]

Analog Input (1 to 2)

TC Linearization

Set the linearization to

match the thermocouple

wired to this input.

[```b]

B (11)

[```H]

K (48)

[```C]

C (15)

[```n]

N (58)

[```d]

D (23)

[```r]

R (80)

[```E]

E (26)

[```S]

S (84)

[```F]

F (30)

[```t]

T (93)

[```J]

J (46)

J

Instance 1

Map 1 Map 2

370 370

Instance 2

Map 1 Map 2

450

460

0x68 (104)

1 to 2

6

4

4006

uint

RWES

[`Rt;L]
[ rt.L]

Analog Input (1 to 2)

RTD Leads

Set to match the num-

ber of leads on the RTD

wired to this input.

[```2]

2 (1)

[```3]

3 (2)

2

Instance 1

Map 1 Map 2

372 372

Instance 2

Map 1 Map 2

452

462

0x68 (104)

1 to 2

7

- - - -

4007

uint

RWES

[Unit]
[Unit]

Analog Input (1 to 2)

Units

Set the type of units the

sensor will measure.

[`A;tP]

Absolute Temperature

(1540)

[``rh]

Relative Humidity

(1538)

[`Pro]

Process (75)

[PWr]

Power (73)

Process

Instance 1

Map 1 Map 2

- - - -

442

Instance 2

Map 1 Map 2

- - - -

532

0x68 (104)

1 to 2

0x2A (42)

5

4042

uint

RWES

[`S;Lo]
[ S.Lo]

Analog Input (1 to 2)

Scale Low

Set the low scale for pro-

cess inputs. This value,

in millivolts, volts or mil-

liamps, will correspond to

the Range Low output of

this function block.

-100.0 to 1,000.0

0.0

Instance 1

Map 1 Map 2

388

388

Instance 2

Map 1 Map 2

468

478

0x68 (104)

1 to 2

0xF (15)

6

4015

float

RWES

[`S;hi]
[ S.hi]

Analog Input (1 to 2)

Scale High

Set the high scale for

process inputs. This

value, in millivolts, volts

or milliamps, will corre-

spond to the Range High

output of this function

block.

-100.0 to 1,000.0

20.0

Instance 1

Map 1 Map 2

390

390

Instance 2

Map 1 Map 2

470

480

0x68 (104)

1 to 2

0x10 (16)

7

4016

float

RWES

[`r;Lo]
[ r.Lo]

Analog Input (1 to 2)

Range Low

Set the low range for this

function block's output.

-1,999.000 to 9,999.000

0.0

Instance 1

Map 1 Map 2

392

392

Instance 2

Map 1 Map 2

472

482

0x68 (104)

1 to 2

0x11 (17)

8

4017

float

RWES

Note:
Some values will be rounded off to fit in the four-character display. Full values can be read
with other interfaces.

R: Read

W: Write

E:

EEPROM

S:

User

Set