beautypg.com

Watlow ez-zone, Pm integrated controller, Chapter 2 install and wire – Watlow EZ-ZONE PM Integrated Controller User Manual

Page 26: Terminal definitions for slot c, Back view slot orientation 1/8 din horizontal pm9, Back view slot orientation 1/8 din vertical pm8

background image

Watlow EZ-ZONE

®

PM Integrated Controller

23

Chapter 2 Install and Wire

Communications

Terminal Function

Configuration

CB

CA

CC

CB

CA

C5

C3

C2

CB

CA

CC

CB

CA

C5

C3

C2

Modbus RTU EIA-485 T+/R+

Modbus RTU EIA-485 T-/R-

Modbus RTU EIA-485 common

Modbus RTU EIA-485 T+/R+

Modbus RTU EIA-485 T-/R-

Modbus RTU EIA-232 common

Modbus RTU EIA-232 to DB9 pin 2

Modbus RTU EIA-232 to DB9 pin 3

Modbus RTU 232/485 Communications

Slot B: PM6 _ _ _ _ - [2] A A A _ _ _

Slot E: PM[4,8,9] _ _ _ _ - [2] _ _ _ _ _ _

V+

CH

SH

CL

V-

V+

CH

SH

CL

V-

DeviceNet™ power

Positive side of DeviceNet™ bus

Shield interconnect

Negative side of DeviceNet™ bus

DeviceNet™ power return

DeviceNet™ Communications

Slot B: PM6 _ _ _ _ - [5] A A A _ _ _

Slot E: PM[4,8,9] _ _ _ _ - [5] _ _ _ _ _ _

E8

E7

E6

E5

E4

E3

E2

E1

E8

E7

E6

E5

E4

E3

E2

E1

EtherNet/IP™ and Modbus TCP unused

EtherNet/IP™ and Modbus TCP unused

EtherNet/IP™ and Modbus TCP receive -

EtherNet/IP™ and Modbus TCP unused

EtherNet/IP™ and Modbus TCP unused

EtherNet/IP™ and Modbus TCP receive +

EtherNet/IP™ and Modbus TCP transmit -

EtherNet/IP™ and Modbus TCP transmit +

Ethernet 10/100 supporting EtherNet/IP™

and Modbus TCP

Slot B: PM6 _ _ _ _ - [3] A A A _ _ _

Slot E: PM[4,8,9] _ _ _ _ - [3] _ _ _ _ _ _

VP

B

A

DG

trB

B

A

trA

VP

B

A

DG

trB

B

A

trA

Voltage Potential

EIA-485 T+/R+

EIA-485 T-/R-

Digital ground (common)

Termination resistor B

EIA-485 T+/R+

EIA-485 T-/R-

Termination resistor A

Profibus Communications

Slot B: PM6 _ _ _ _ - [6] A A A _ _ _

Slot E: PM [4, 8, 9] _ _ _ _- [6] A A A A A A

Slot A

Slot B

Slot D

Slot E

Terminal Definitions for Slot C .

Slot C Terminal Function

Configuration

98

99

Power input: ac or dc+

Power input: ac or dc-

all

CC

CA

CB

Standard Bus or Modbus RTU EIA-485 common

Standard Bus or Modbus RTU EIA-485 T-/R-

Standard Bus or Modbus RTU EIA-485 T+/R+

Standard Bus or Modbus

PM _ _ _ _ _ - [1] _ _ _ _ _ _

CF

CD

CE

Standard Bus EIA-485 common

Standard Bus EIA-485 T-/R-

Standard Bus EIA-485 T+/R+

PM _ _ _ _ _ - [A,D,2,3,5] _ _ _ _ _ _

B5

D6

D5

Digital input-output common

Digital input or output 6

Digital input or output 5

PM _ _ [2] _ _ - _ _ _ _ _ _ _

PM _ _ [4] _ _ - _ _ _ _ _ _ _

A

Output 2

Output 1

Input 1

B

Output 3

Output 4

Input 2

D

Digital I/O 7 - 12

E

Communications Card

C

Dig I/O 5 & 6

485 Comms

Power

Back View

Slot Orientation

1/8 DIN Horizontal PM9

C

Dig I/O 5 & 6

485 Comms

Power

E

Communications Card

A

Output 2

Output 1

Input 1

B

Output 3

Output 4

Input 2

D

Digital I/O 7 - 12

Back View

Slot Orientation 1/8

DIN Vertical PM8