Process value menu – Watlow EZ-ZONE PM Integrated Controller User Manual
Page 58
![background image](/manuals/359085/58/background.png)
Watlow EZ-ZONE
®
PM Integrated Controller
•
55
•
Chapter 5 Operations Page
Operations Page
Dis-
play
Parameter name
Description
Range
Default
Modbus
Relative Ad-
dress
CIP
Class
Instance
Attribute
hex (dec)
Profibus
Index
Param-
eter ID
Data
Type
& Read/
Write
[``o;u]
[ o.v]
Linearization (1 to 2)
Output Value
View the value of this
function's output.
-1,999.000 to 9,999.000°F
or units
-1,128.000 to 5,537.000°C
Instance 1
Map 1 Map 2
- - - -
3572
Instance 2
Map 1 Map 2
- - - -
3642
0x86 (134)
1 to 2
7
- - - -
34007
float
R
No
Dis-
play
Linearization (1 to 2)
Output Error
View reported cause for
Linearization output
malfunction.
[none]
None (61)
[open]
Open (65)
[shrt]
Shorted (127)
[`e;m]
Measurement er-
ror (140)
[e;Cal]
Bad calibration
data (139)
[er;ab]
Ambient error (9)
[e;rtd]
RTD error (14)
[fail]
Fail (32)
[er;m]
Math error (1423)
[nSrc]
Not sourced (246)
[stal]
Stale (1617)
[no;pr]
Can't process
(1659)
None
Instance 1
Map 1 Map 2
- - - -
3614
Instance 2
Map 1 Map 2
- - - -
3684
0x86 (134)
1 to 2
0x1C (28)
- - - -
34028
uint
R
[``Pu]
[oPEr]
Process Value Menu
[`Su;A]
[ Sv.A]
Process Value (1 to 2)
Source Value A
View the value of Source
A.
Linearization 1 is con-
nected to Source A of
Process Value 1
Linearization 2 is con-
nected to Source A of
Process Value 2
-1,999.000 to 9,999.000°F
or units
-1,128.000 to 5,537.000°C
Instance 1
Map 1
Map 2
- - - -
3310
Instance 2
Map 1
Map 2
- - - -
3380
0x7E (126)
1 to 2
0x10 (16)
- - - -
26016 float
R
[`Su;b]
[ Sv.b]
Process Value (1 to 2)
Source Value B
View the value of Source
B.
Linearization 2 is con-
nected to Source B of
Process Value 1
Linearization 1 is con-
nected to Source B of
Process Value 2
-1,999.000 to 9,999.000°F
or units
-1,128.000 to 5,537.000°C
Instance 1
Map 1
Map 2
- - - -
3312
Instance 2
Map 1
Map 2
- - - -
3382
0x7E (126)
1 to 2
0x11 (17)
- - - -
26017 float
R
[oFSt]
[oFSt]
Process Value (1 to 2)
Offset
Set an offset to be ap-
plied to this function's
output.
-1,999.000 to 9,999.000°F
or units
-1,128.000 to 5,537.000°C
0
Instance 1
Map 1
Map 2
- - - -
3324
Instance 2
Map 1
Map 2
- - - -
3394
0x7E (126)
1 to 2
0x17 (23)
- - - -
26023 float
RWES
Note:
Some values will be rounded off to fit in the four-character display. Full values can
be read with other interfaces.
R: Read
W: Write
E: EEPROM
S: User
Set