Ez-zone, Watlow ez-zone, Pm integrated controller – Watlow EZ-ZONE PM Integrated Controller User Manual

Page 11: Chapter 1 overview, Input functions output functions

background image

Watlow EZ-ZONE

®

PM Integrated Controller

8

Chapter 1 Overview

EZ-ZONE

®

PM Integrated Model 1/16 DIN System Diagram

With a Current Transformer, Without Communications Card (Slot B)

Note:

Number of inputs and outputs and various combinations of the same will vary

depending upon part number; see ordering matrix for more detail.

EZ Key

Programmable Event

Digital Output (or Input) 5 & 6

(optional) none, switched dc

Digital Input (or Output) 5 & 6

(optional) none, switch, volts dc

Current

Transformer

Board

(optional)

Slot B

Input

Functions

Output

Functions

- None

- Idle set point

- Tune

- Alarm clear, request

- Force alarm

- Silence alarm

- Manual/auto mode

- Control outputs off

- Remote set point

enable

- Lock keypad

- TRU-TUNE+

®

disable

- Loop & alarms off

- Profile disable

- Profile hold/resume

- Profile start

- Profile start/stop

- Restore user settings

- Event inputs

Output Status

5

1

3

2

4

Indicates Zone

Address

Indicates I/O

Status

Zone

Address

Analog Input 1

none, Thermocouple, RTD (100Ω,

1kΩ), Thermistor 5kΩ, 10kΩ, 20kΩ,

40kΩ) Process (V, mV, mA) or 1k

Potentiometer

Output 1

none, switched dc/open collector, 5A

mechanical relay (form C), process

(V, mA), or 0.5A SSR (form A)

Output 2

none, 15A NO-ARC, switched dc,

5A mechanical relay (form A), or

0.5A SSR (form A)

Analog Input 2

Current Transformer

PID

Controller

(Optional -

Ramp/Soak max 4

files, 40 steps)

Slot A

(Optional)

Input Sensor

off, heat, cool

alarm, retransmit,

duplex, event

off, heat, cool

alarm, event

off, heat, cool

alarm, retransmit,

duplex, event

off, heat, cool

alarm, event

off, heat, cool

alarm, event

Modbus

Address

1 - 247

Standard Bus

Zone Address

1 - 16

Supervisory &

Power Board

Slot C

Current

Transformer

EIA-485 Communication

Standard Bus

(optional Modbus RTU)

RUI, EZ-ZONE

Controllers, PLC, PC

or HMI

Output 3

none, switched dc/open collector, 5A

mechanical relay (form C), process

(V, mA), or 0.5A SSR (form A)

Output 4

none, 15A NO-ARC, switched dc,

5A mechanical relay (form A), or

0.5A SSR (form A)

6

Current Monitoring
detects heater current flow
provides an alarm indication of a failed-load issue.