Error t reatment 104 – IAI America XSEL-S User Manual
Page 110
7. Error
T
reatment
104
Info1
Info2
Cause
Treatment Detail
68h
(104)
-
Each Axis
Parameter
No.104
Multi-Slider Function is set to 2 axes in those specified
for the coordinate axes definition. Vision system I/F
Function cannot be used together with Multi-Slider
Function.
Set Each Axis Parameter No.104 = 0.
79h
-
-
*Please contact us.
15Fh
(351)
-
I/O Parameter
No.351
Bit4-7
There is an error in the communication device setting.
Set a value within the range of 0 to 5.
[Refer to 5.7 Parameter Setting]
160h
-
I/O Parameter
No.352
Bit0-7
There is an error in the communication format.
Set a value within the range of 0 to 2.
[Refer to 5.4 Communication Format Setting]
164h
-
I/O Parameter
No.356
There is an error in Initializing Complete Status
Physical Input Port Number. Specify the port number
within the specifiable range.
165h
-
I/O Parameter
No.357
Either the Image-Capture Trigger Output Port Number
is duplicated with another function, or a port number
out of the range is specified. Check the port number.
Treatment
(Error No. D8C
Continued)