Caution – IAI America XSEL-KET User Manual
Page 42

23
INTELLIGENT ACTUATOR
Part 1 Installation
(2) Output
part
External Output Specifications (PNP Specification)
Item
Specification
Load voltage
24 VDC
Maximum load current 100 mA per point, 400 mA per 8 ports Note)
Leakage current
0.1 mA max. per point
TD62784 (or equivalent)
Insulation method
Photocoupler insulation
External devices
(1) Miniature relay
(2) Sequencer input unit
Note) 400 mA is the maximum total load current of every eight ports from output port No. 300. (The
maximum total load current of output port No. 300 + n to No. 300 + n + 7 is 400 mA, where n is 0
or a multiple of 8.)
[Output circuit]
* P24: I/O24V power connector, 24V IN
* N:
I/O24V power connector, 0V
Caution
In the event that the load is short-circuited or a current exceeding the maximum load
current is input, the overcurrent protection circuit will be actuated to cut off the circuit.
However, give due consideration to the circuit connection layout to prevent short-circuit
or overcurrent.
Internal circuit
10
N
P24
Surge absorber
Output terminal
Load
External power supply
24 VDC
10%
+
-