Chapter 1 Specifications Check
POWER CON
PCON-CA/CFA
32
1.4.2 Pulse Train Input Output Interface
Line Driver Input
Specification
Sends input pulse from the host unit that is installed with a line
driver 26C31 or equivalent
Host Unit
Positioning Unit
PCON
PP
/PP
NP
/NP
Pulse Train
Form
Including active high and active low
1.5
Options
1.5.1 Pulse converter : AK-04
The pulse converter converts command pulses in the open collector mode to those in the
differential mode.
Use this converter if the host controller sends output pulses in the open collector mode.
Item
Specification
Input Power
Supply
24V DC r10% (MAX. 50mA)
Input Pulse
O/C (Collector current MAX. 12mA)
Input Frequency 200kpps or less
Output Pulse
Differential output equivalent to 26C31 (MAX. 10mA)
Mass
10g or less (excluding cable connector)
Accessories
37104-3122-000FL (e-CON Connector) 2 Units
Cover Color : YW
Applicable wire AWGNo.24 to 26 (Less than 0.14 to 0.3mm
2
,
finished O.D. I1.0 to 1.2mm)
Caution
1) Use the pulse converter in the surrounding temperature range between 0qC and
40qC.
2) The temperature increase of about 30qC occurs during operation. Accordingly,
neither install several pulse converters in close contact nor install them within a
duct. Do not install the pulse converter near other heating devices.
3) If more than one pulse converter are installed, set a pulse converter apart from
another by 10mm or more.