Pcon-ca/cfa, Power con, Pulse train control mode (for pulse train type) – IAI America PCON-CA User Manual

Page 28

background image

POWER CON

PCON-CA/CFA

20

2. Pulse Train Control Mode (for Pulse Train Type)

This product is capable for the positioning control using the pulse train of IAI actuators.

It is necessary to have the positioning control function able to output the pulse train on the host

controller (PLC).

When using this product for the first time, make sure to avoid mistakes and incorrect wiring by

referring to the procedure below. “PC” stated in this section means “PC software”.

Set the Electronic Gear [Refer to 3.3.4 [1]]

Set the electronic gear ratio based on the

amount of actuator operation per pulse in

Parameters No.65 and 66.

ψ

Check Item

Is the minimum unit of operation set to the value bigger than the

minimum resolution of the encoder?

Is the fraction of the electronic gear ratio reduced to its lowest terms?

φ

Yes

Pulse Train Input Output Mode Setting [Refer to 3.3.4 [2]]

Set the command pulse train input status for the parameter No.63 and No.64.

Put Operation Mode Setting Switch to “AUTO” side when the setting is complete.

Servo ON

Input servo ON signal from PLC.

ψ

Check Item

Is the Controller Status

Display LED turned ON

in green [SV]?

No ψ

Confirm the content of alarm on the teaching

tool such as PC to have an appropriate

treatment.

φ

Yes

Safety Circuit Check

Check that the emergency stop circuit (or motor

drive-power cutoff circuit) operates normally to turn

OFF the servo.

No ψ

Check the emergency stop circuit.

ω

Yes

ψ

No ψ

Contact us or our distributor.

ω

Yes

No ψ

ψ

Check Item

Is the Controller Status

Display LED turned OFF?

Connect the teaching tool

such as PC to confirm the

content of alarm and have

an appropriate treatment.

Test Run Adjustment 2

[Operation Mode AUTO]

Output the pulse train from PLC to

the controller and check the

system operation.

ψ

No ψ

No ψ

Check the electronic gear ratio setting.

Confirm the command pulse train input mode

setting.

Confirm that there is no problem in the

actuator installation, the actuator operation

condition demands a voltage more than rated

voltage, and appropriate pulse trains are input.

Power Supply and Alarm Check

Connect a teaching tool such as PC, turn the

operation mode setting switch to “MANU” side and

turn the power ON for unit.

Select [Teaching Mode 1 Safety Speed Activated /

PIO Operation Invalid] in the teaching tool.

ω

Yes

φ

Yes

Check of Packed Items

Are there all the delivered items?

Installation and Wiring [Refer to Chapter 1, 2.2, 2.3]

Perform the installation of and wiring for the actuator and

controller.

Point Check Item

• Is frame ground (FG) connected?

• Has the noise countermeasure been taken?

ψ

Test Run Adjustment 1

[Operation Mode MANU]

Check with a teaching tool such as the

PC with no work being loaded, and check

the operation range with JOG operation

with the work being loaded.

Check if there is any problem in the way of

actuator mount.

Check Item

Is there any risk of

interfering with

peripheral

equipment?

Yes ψ

ω

No

Can the positioning

operation be performed

normally?

ω

Yes

ω

Yes

Is it in condition without

any vibration and

abnormal noise?

Test Run Adjustment 3

Check the system operation conducted by PLC.

PIO Pattern Settings

Set the used PIO pattern to Parameter No.25.