Chapter 8
Troubleshooting
POWER CON
PCON-CA/CFA
213
Alarm
Code Alarm Level
Alarm Name
Cause/Treatment
0D5
Cold start
Differential Counter
Overflow with Home
Return Incomplete
Cause
: This alarm indicates that the position deviation
counter has overflowed.
1) The speed dropped or stopped during JOG
move due to an impact of external force, hit to
the mechanical end or overload.
2) The excited-phase detection operation
following the power-on is unstable.
Treatment : 1) This error occurs when the actuator cannot be
operated as it is commanded. Check the load
conditions such as if the work is touching to
the surrounding object, or brake is properly
released, and remove the cause.
2) Overload is concerned. Revise the
transportable weight.
0D6
FAN error detection
Cause
: Error detected on heatsink fan inside the
controller
Treatment : If occurs, please contact IAI.
0D8
Deviation overflow
Cause
: This alarm indicates that the position deviation
counter has overflowed.
1) The speed dropped or the actuator stopped
due to the effect of external force or overload.
2) The excited-phase detection operation
following the power-on is unstable.
Treatment : 1) This error occurs when the actuator cannot be
operated as it is commanded. Check the load
conditions such as if the work is touching to
the surrounding object, or brake is properly
released, and remove the cause.
2) Overload can be concerned. Revise the
transportable weight and redo the
home-return operation.
0D9
Software stroke limit
exceeded
Cause
: The current position of the actuator exceeds the
software stroke limit.
Treatment : Return the actuator to be within the range of the
software stroke limit.
0DC
Operation
release
Pressing motion range
over error
Cause
: 1) After the pressing operation has complete,
the force to push back is too large and the
pushed back to the pressing start position
(“Position” in the position table).
2) The actuator touched the work during the
approach movement before the pressing
movement.
Treatment : 1) Revise the setting and adjust it so the force to
push back gets smaller.
2) Set the “Position” setting in front in the
position table to shorten the approach
distance.