beautypg.com

23 preset point output function, Preset point output functions, To change the preset output function – Toshiba LF600F User Manual

Page 98: Toshiba, Output status level hold, Pulse out (pulse width 50ms), Pulse out (pulse width 500ms)

Attention! The text in this document has been recognized automatically. To view the original document, you can use the "Original mode".

background image

TOSHIBA

i6,R8,A0,8,6,9,

8.2.23 Preset Point Output Function

The output function when a preset counter becomes the preset value can be set.
The various preset point output functions shown below can be selected.

■ Preset Point Output Functions

DI function

Preset point output level function

HOLD

Output status level hold

50ms PULSE

Pulse out (pulse width 50ms)

500ms PULSE

Pulse out (pulse width 500ms)

Note: If you set the preset point output function to "50ms PULSE" or "500ms PULSE", you need to
set the preset count value to 1,2, 5, 25, 125x10". (If you set a value that does not meet this condition,
the preset point output timing may be shifted when a total counter overflow occurs.

Proceed as follows to check or change the preset point output functions.

• To change the preset output function

The following example shows how to change the present output function from Output condition
hold (HOLD) to One-shot pulse output with pulse width of 50ms (50ms PULSE).

Key operation

Display example

Description

H:

Select "PRESET FNC" in the configuration item selection

MEAS MODE
PRESET CNT

^PRESET FNC

[SEL] [ENT]

screen.

STEP1

H2:

The current setting value is displayed (HOLD in this

PRESET FNC

HOLD

example).

[ENT]

[EXT] [ENT]

Then press the [ENT] key.
* Pressing the [EXT] key returns you to the menu screen.

STEP2

H2:

The switch name display at the bottom changes (three

PRESET FNC

keys [UP], [DOWN] and [SET]).

bb

I

bi

At the same time, the cursor appears.

[ENT]

(The digit on which the cursor is positioned is

[U PI fDWNl [SET]

reverse-displayed.)

STEP3

H2:

PRESET FNC

Change the selection item using the [UP]/[DWN] key.

When you have selected the desired item, press the [SET]

[UP]/[DWN]

[U P] [DWN] [SET]

key.

STEP4

H2:

When you press the [SET] key, the selected item is set

PRESET FNC

temporarily and a message confirming you whether the

50ms PULSE

setting is OK is displayed.

[SET]

A

If OK, press the [SET] key. If you want to redo the setting.

OK? ®

[NO] [SET!

press the [NO] key.

STEP5-1

H2:

Pressing the [NO] key when you are asked "OK?" causes

PRESET FNC

the setting to return to the previous state and enables you

[NO]

BBIBI

to redo the setting.

[U PI fDWNl [SET]

STEP5-2(=END)

H2:

Pressing the [SET] key when you are asked "OK?" causes

PRESET FNC

the setting to be determined.

50ms PULSE

Then, press the [EXT] key. You return to the menu screen.

[SET]

[EXT] [ENT]

Pressing the [ENT] key enables you to restart

setting operation from a state of 50ms PULSE.

-

97

-

This manual is related to the following products: