8.2.23 Preset Point Output Function
The output function when a preset counter becomes the preset value can be set.
The various preset point output functions shown below can be selected.
■ Preset Point Output Functions
DI function
Preset point output level function
HOLD
Output status level hold
50ms PULSE
Pulse out (pulse width 50ms)
500ms PULSE
Pulse out (pulse width 500ms)
Note: If you set the preset point output function to "50ms PULSE" or "500ms PULSE", you need to
set the preset count value to 1,2, 5, 25, 125x10". (If you set a value that does not meet this condition,
the preset point output timing may be shifted when a total counter overflow occurs.
Proceed as follows to check or change the preset point output functions.
• To change the preset output function
The following example shows how to change the present output function from Output condition
hold (HOLD) to One-shot pulse output with pulse width of 50ms (50ms PULSE).
Key operation
Display example
Description
H:
Select "PRESET FNC" in the configuration item selection
MEAS MODE
PRESET CNT
^PRESET FNC
[SEL] [ENT]
screen.
STEP1
H2:
The current setting value is displayed (HOLD in this
PRESET FNC
HOLD
example).
[ENT]
[EXT] [ENT]
Then press the [ENT] key.
* Pressing the [EXT] key returns you to the menu screen.
STEP2
H2:
The switch name display at the bottom changes (three
PRESET FNC
keys [UP], [DOWN] and [SET]).
bb
I
bi
At the same time, the cursor appears.
[ENT]
(The digit on which the cursor is positioned is
[U PI fDWNl [SET]
reverse-displayed.)
STEP3
H2:
PRESET FNC
Change the selection item using the [UP]/[DWN] key.
When you have selected the desired item, press the [SET]
[UP]/[DWN]
[U P] [DWN] [SET]
key.
STEP4
H2:
When you press the [SET] key, the selected item is set
PRESET FNC
temporarily and a message confirming you whether the
50ms PULSE
setting is OK is displayed.
[SET]
A
If OK, press the [SET] key. If you want to redo the setting.
OK? ®
[NO] [SET!
press the [NO] key.
STEP5-1
H2:
Pressing the [NO] key when you are asked "OK?" causes
PRESET FNC
the setting to return to the previous state and enables you
[NO]
BBIBI
to redo the setting.
[U PI fDWNl [SET]
STEP5-2(=END)
H2:
Pressing the [SET] key when you are asked "OK?" causes
PRESET FNC
the setting to be determined.
50ms PULSE
Then, press the [EXT] key. You return to the menu screen.
[SET]
[EXT] [ENT]
Pressing the [ENT] key enables you to restart
setting operation from a state of 50ms PULSE.
-
97
-