6. Operation
A CAUTION
■ Do not touch the terminal board when power is
■ Do not touch the main body when high temperature
supplied.
fluid is being measured.
Touching the terminal board when
The fluid raises the main body
V^y power is supplied can cause
temperature and can cause bums.
DON’T
6l®ctric shock.
DON’T
6.1 Preparatory check
Follow the procedure described below to prepare before starting the flow measurement
(described with regard to the entire flowmeter).
System Check
Check the items listed below
Check the wiring between the converter and related instruments.
Make sure all the bolts of connection flanges on which the flowmeter is mounted
securely tightened.
Make sure the direction of flow arrow is in accordance with actual flow.
Make sure the flowmeter is grounded with 100 ohm or less ground resistance.
Make sure the converter housing covers are securely tightened.
Placing System On-Stream
Let the fluid go through the detector pipe. (Note 1)
When the detector is filled with the fluid, stop the fluid and keep it still in the detector pipe.
Supplying Electric Power
Make sure the power supply is as specified.
Checking Converter Parameters
Check the configuration parameter settings. Refer to Chapter 7, “LCD Display and
Controls,” Chapter 8, “Configuration Parameter Setting,” and Chapter 11,
“Communications Function.”
Zero Adjustment
Wait for 30 minutes to warm up the flowmeter. Then making sure the fluid holds still in the
detector pipe, starts the zero adjustment.
Refer to 6.2, “Zero Adjustment.”
On-line measurement
■ After checking the items and conducting the zero adjustment as listed above, let the fluid go
through the detector pipe. Output (4-20 mA dc) directly proportional to the flow rate can be
obtained.
Note 1: If the detector pipe is not filled with the fluid to be measured, the flow rate will be
indefinite and unable to be measured. Before using the flowmeter , be sure to fill the detector
pipe the fluid to be measured.
-
32
-