Multiple range high/low limit alarm output

Flow rate

Note 1: Range changes to Small range when range select signal is H level, and to Large range in

L level.

Note 2: High-high/low-low limit alarm is activated when Small range is selected. High/low limit

alarm is not output to display.
High/low limit alarm is activated when Large range is selected. High-high/low-low limit
alarm is not output to display.

Note 3: Alarm output state is the same state to which digital output 1 or 2 is set. When converter

power is OFF, contact output is OPEN.

Note 4: Each alarm set value % is the percent set to the first range.

Note 5: Hysteresis of each alarm is 2.5 % for the first range.

Example

When Large range and Small range are set as below:

Large range (Range 1):

1000 m^/h

Small range (Range 2):

500 m^/h

And you want to set alarm values as below:

Large range alarm set values

High limit value:

800 m^/h

Low limit value:

600 m^/h

Small range alarm set values

High-high limit value: 400 m^/h
Low-low limit value: 300 m^/h

Set the alarm set values as below:

High limit value:
Low limit value:

80 % (800 m^/h

-1000

m^/h=

0

.

8

)

60 % (600 m^/h

4-1000

m^/h=

0

.

6

)

High-high limit value: 40 % (400 m^/h-blQOQ m^/h=0.4)
Low-low limit value: 30 % (300 m^/h-blQOQ m^/h=0.3)

See Note4.
See Note4

-