8.2.29 Fixed-Value Output
The fixed-value output is used to output a fixed current and a fixed pulse output independently of
the flow rate signal. (The fixed pulse output is available only when DOl is used for PULSE OUT
function.) Fixed pulse cannot be output from D02 (optional).
The fixed-value output can be set in the ranges described below. (Current output and pulse output can
be set and output at the same time.)
• Fixed current output: 2.4 to 24 mA (in increments of 0.1 mA)
• Fixed pulse output:
0 to lOOOpps (in increments of 1 pps)
If fixed output is ON, the sub display is used for fixed output display in the measurement mode.
Operation when fixed output is ON
Current output
Set current output
Pulse output
Pulse output at the set pulse rate
Digital output other than pulse
State held
Display
Sub display: Used for fixed output display
(Totalization is not perforhied.)
Display example:
! *
F
1
X
E
D
0
u
T
♦
*
1
0
0
0
0
p
P S
♦
♦
0
0
m A
♦
Current output value (4-digit display including decimal point).
The unit is (mA) fixed.
Pulse display (max. 5 digits). The unit is (PPS) fixed.
This fixed-value output function does not work in the calibration mode.
When OFF is selected in the fixed output function, setting for output is not needed.
Proceed as follows to check or change the enable/disable status of the fixed-value output and its output
values.
Fixed-value output enable/disable status and its output values, fixed current output and fixed pulse
output can be selected by the configuration items as follows:
Fixed-value enable/disable status
Fixed current output
Fixed pulse output
LI: FIXED OUT
L2: FIXED CURR
L3: FIXED PULSE
-
105
-