beautypg.com

6|f|8ia0i8,6i9i, Toshiba – Toshiba LF600F User Manual

Page 100

Attention! The text in this document has been recognized automatically. To view the original document, you can use the "Original mode".

background image

TOSHIBA

6|F|8iA0i8,6i9i

Changing the high, low, high-high, or low-low limit alarm value

Shown below is an example of changing the high limit alarm value from +105% to +103%.

Key operation

Display example

Description

I:

MEAS MODE
HALM SET

ALM VAL

LALM SET
L ALM VAL

[SEL] [ENT]

Select "HALM VAL" in the configuration item

selection screen.

STEP1

[ENT]

I2:

HALM VAL

+105.0

%

[EXT] [ENT]

The currently set value (+105.0 in this example) is

displayed.

Then press the [ENT] key.

* Pressing the [EXT] key returns you to the menu
screen.

STEP2

[ENT]

I2:

HALM VAL

B105.0

%

[U P] [SEL] [SET]

The switch name display at the bottom changes

(three keys [UP], [SEL] and [SET]).

At the same time, the cursor appears.

(The digit on which the cursor is positioned is

reverse-displayed.)

STEPS

[SEL]0[UP]

12:

H ALM VAL

+10|.0

%

[U P] [SEL] [SET]

Move the cursor to the desired digit using the [SEL]

key and change the numeric value using the [UP]

switch.

Repeat this operation to change the value to

+103.0%.

When you have selected the desired item, press

the [SET] key to set the value temporarily.

STEP4

[SET]

12:

H ALM VAL

+103.0

%

OK?

^

[NOl [SETl

When you press the [SET] key, a message
confirming you whether the setting is OK is

displayed.

If OK, press the [SET] key. If you want to redo the

setting, press the [NO] key.

STEP5-1

[NO]

12:

H ALM VAL

B105.0

%

[U P] [SEL] [SETl

Pressing the [NO] key when you are asked "OK?"

causes the numeric value to return to the previous

value and enables you to redo the setting.

STEP5-2(=END)

[SET]

12:

HALM VAL

+103.0

%

[EXT] [ENT]

Pressing the [SET] key when you are asked "OK?"

causes the setting to be determined.

Press the [EXT] key. You return to the menu

screen.

Pressing the [ENT] key enables you to restart
setting value change operation from a state of

+103.0%.

Note: If you set a value that is not within a range of -10% to +110%, * LOW OVER SPEC* or

♦HIGH OVER SPEC* is displayed and the value returns to the one before change. Set a

value once again.

-