10. Digital I/O Functions

The LF60*F series electromagnetic flowmeter is equipped with two-contact-point terminals (digital
output terminals: one of them is optional), enabling you to use various functions including pulse
output and alarm output.

Digital I/O functions are described below.

Functions

Necessary DO/DI

Description

Totalization

DO: 1 point

DI: None to

1 point

■ The converter totalizes volumetric flow rate.

■ The totalized volumetric flow can be output (pulse output)

for each unit flow.

■ The totalizer and pulse signal (DOl only) can be controlled

(starts, stops and resets) with an external signal (DI).

Multiple Ranges

DO: 1 to

2 points

DI: None to

1 point

Multiple measuring ranges can be switched according to

the process flow rates either automatically or by an external

signal (DI).

Forward and

Reverse flow

measurements

DO: 1 point

■ Forward and reverse flows can be measured. The forward

and reverse flow measurements can be used together with

multiple range switching function.

High and Low

Limit Alarms

DO: 1 to

2 points

■ Outputs an alarm signal (DOl or D02) when the process

signal exceeds or stays below the limit values.

Totalizer Preset

Point

DO: 1 point

■ When the totalized flow exceeds its preset count value, the

converter outputs a contact output signal (DOl or D02).

Remote Zero
Adjustment

DI: 1 point

■ Zero adjustment (on-stream at zero flow rate) can be started

by an external signal (DI).

Fixed-value

Output

DI: 1 point

■ Fixed current output and fixed pulse output can be used to

check a process loop circuit. An external signal (DI) can also

be used to control this fixed-value output.

Converter

Failure Alarm

DO: 1 point

■ The converter outputs an alarm signal (DOl or D02) if

an error such as memory error or excitation circuit error

occurs.

Multiple range
High/Low alarm

(option)

DO: 2 points
DI: 1 point

■ Flow rate high/low alarm and high-high/low-low alarm

are switched interlocking with the switching of high/low

range by external input signal, and output HH/LL alarm.

-