beautypg.com

I preset count output performance, Toshiba – Toshiba LF600F User Manual

Page 129

Attention! The text in this document has been recognized automatically. To view the original document, you can use the "Original mode".

background image

TOSHIBA

i6,F,8,A0,8,6,9,

I

Preset count output performance

(l)The following is an example for totalizer flow counts output in which the totalizer is reset with an

external signal (when preset output status level hold mode is set (contact ON)).

H level input

Counter Reset/Start signal

(DI detective level is H).

Totalizer flow counts

n

Counter reset

Counter start

Counter reset

Preset point output

L level input

Preset point

ON

OFF

Input/Output signal time chart

* When the Reset/Start signal is in H level (DI counter control signal level: H), the totalizer

is reset to zero and stops counting. When the Reset/Start signal goes to L level, the
totalizer starts counting. The preset point output goes ON when the totalizer counts

reaches the preset point, and the output goes OFF when the totalizer is reset to zero.

(2)The following is an example for totalizer flow counts output in which the totalizer is reset with an

external signal (when one-shot pulse output mode is set).

H level input

L level input

Preset point

ON

OFF

the preset output goes OFF.

the output goes OFF

Input/Output signal time chart

* When the Reset/Start signal is in L level (DI counter control signal level: L), the totalizer is

reset to zero and stops counting. When the Reset/Start signal goes to H level, the totalizer

starts counting.

The preset point output goes ON when the totalizer counts reaches the preset point. The
output goes OFF when the totalizer is reset to zero or when it takes the time set pulse
width from the output goes ON.

-

128

-

This manual is related to the following products: