3 ras settings in the »engineer, Ras settings in the »engineer, Industrial pc | parameter setting & configuration – Lenze PC-based Automation Industrial PC User Manual
Page 85

2.5 EN - 01/2012
L
85
Industrial PC | Parameter setting & configuration
Remote maintenance and diagnostics
Remote Access Service (RAS) connection
12.1.3
RAS settings in the »Engineer«
The IPC assigns a generated IP address to the clients of the RAS connection. To access the
IPC via a client PC, enter the IP address of the IPC in the
»Engineer«.
The server IP address is the address of the Industrial PC,
The client IP address is the address of the client PC.
The RAS server is activated in the standard setting on the Industrial PC, so that the
reception of calls does not require manual settings. The standard settings can be changed
in the »Engineer«.
How to change the connection settings in the »Engineer«:
1. Select the Industrial PC the connection settings of which are to be changed,
2. If the Industrial PC is not connected, right-click on the IPC and select Go online,
3. Click the All parametersRemote control tab.
• The RAS settings of the Industrial PC can be changed via codes 175 to 179:
Codes
Code 175 activates the RAS server,
Code 176 defines the hardware for the RAS connection,
Code 177 selects the connection type,
Code 178 selects the baud rate,
Code 179 activates routing.