beautypg.com

Industrial pc | parameter setting & configuration, Al status codes – Lenze PC-based Automation Industrial PC User Manual

Page 185

background image

2.5 EN - 01/2012

L

185

Industrial PC | Parameter setting & configuration

Parameter reference

Industrial PC extension modules

C1096/19

AL status codes

Parameter | Name:

C1096/19 | ECAT: Error code

Data type: UNSIGNED_32

Index: 23479.19

d

=

0x5BB7.0x13

h

Display of the AL status code (slave register "0x0134 : 0x0135")

;

Read access … Write access … CINH … PLC STOP … No transfer

Code (hex)

Description

Current state or state

change

Resulting state

0x0000

No error

Arbitrary

Current state

0x0001

Unspecified error

Arbitrary

Arbitrary + E

0x0011

Invalid requested state

IS, IO, PO, OB,

SB, PB

Current state + E

0x0012

Unknown requested state

Arbitrary

Current state + E

0x0013

Bootstrap state is not supported

IB

I + E

0x0014

Invalid Firmware

IP

I + E

0x0015

Invalid mailbox configuration

IB

I + E

0x0016

Invalid mailbox configuration

IP

I + E

0x0017

Invalid sync manager configuration

PS, SO

Current state + E

0x0018

No valid inputs available

O, S, PS

P + E

0x0019

No valid outputs available

O, SO

S + E

0x001A

Synchronisation error

O, SO

S + E

0x001B

Sync manager watchdog

O, S

S + E

0x001C

Invalid sync manager types

O, S

S + E

PS

P + E

0x001D

Invalid output configuration

O, S

S + E

PS

P + E

0x001E

Invalid input configuration

O, S, PS

P + E

0x001F

Invalid watchdog configuration

O, S, PS

P + E

0x0020

Slave requires 'cold boot'

Arbitrary

Current state + E

0x0021

Slave requires 'Initialisation' state

B, P, S, O

Current state + E

0x0022

Slave requires 'Pre-Operational' state

S

S + E

O

O + E

0x0023

Slave requires 'Safe Operational' state

O

O + E

0x0030

Invalid DC configuration

O, S

S + E

0x0031

Invalid DC latch configuration

O, S

S + E

0x0032

PLL error

O, S

S + E

0x0033

DC I/O error

O, S

S + E

0x0034

DC time-out error

O, S

S + E

0x0042

MBX_EOE

B, P, S, O

Current state + E

Legend:
I: Initialisation
B: Bootstrap (is not supported)
P: Pre-Operational
S: Safe Operational
O: Operational
E: Error-Flag