Industrial pc | parameter setting & configuration – Lenze PC-based Automation Industrial PC User Manual
Page 177
2.5 EN - 01/2012
L
177
Industrial PC | Parameter setting & configuration
Parameter reference
Industrial PC extension modules
C1082/1
C1082/2
C1082/3
C1086/2
C1086/3
C1086/4
Parameter | Name:
C1082/1 | ECAT DC: State
Data type: BITFIELD_3
Index: 23493.1
d
=
0x5BC5.0x01
h
Display of the state of the distributed clocks
The bits are set to value 1 if the respective states are reached.
Value is bit-coded:
Bit 0 DC: Activated
Bit 1 DC: Sychronised
Bit 2 DC: Busy
;
Read access Write access CINH PLC STOP No transfer
Parameter | Name:
C1082/2 | ECAT DC: Perm. dev. slave sync
Data type: UNSIGNED_32
Index: 23493.2
d
=
0x5BC5.0x02
h
Permissible deviation of the distributed clocks of all devices in nanoseconds. If the permissible deviation is
exceeded, the master will initiate a resynchronisation of the distributed clocks.
Display range
(min. value | unit | max. value)
0
ns
4294967295
;
Read access Write access CINH PLC STOP No transfer
Parameter | Name:
C1082/3 | ECAT DC: Current deviation
Data type: INTEGER_32
Index: 23493.3
d
=
0x5BC5.0x03
h
Current maximum deviation of the distributed clocks of all devices in nanoseconds.
Display range
(min. value | unit | max. value)
0
ns
2147483647
;
Read access Write access CINH PLC STOP No transfer
Parameter | Name:
C1086/2 | ECAT config.: Checksum CRC-32
Data type: UNSIGNED_32
Index: 23489.2
d
=
0x5BC1.0x02
h
Checksum of the master configuration file (loaded/activated by the stack). The stack determines the checksum of
the loaded/active master configuration file. If this file is not available, the value "0x00000000" will be displayed.
;
Read access Write access CINH PLC STOP No transfer
Parameter | Name:
C1086/3 | ECAT bus: Numb. slaves
Data type: UNSIGNED_32
Index: 23489.3
d
=
0x5BC1.0x03
h
Number of slaves connected to the fieldbus
Display range
(min. value | unit | max. value)
0
4294967295
;
Read access Write access CINH PLC STOP No transfer
Parameter | Name:
C1086/4 | ECATBus: Numb. slaves with DC
Data type: UNSIGNED_32
Index: 23489.4
d
=
0x5BC1.0x04
h
Number of slaves connected to the fieldbus and supported by distributed clocks
Display range
(min. value | unit | max. value)
0
4294967295
;
Read access Write access CINH PLC STOP No transfer